Mounting the Kinetix 2000 Drive System
Mount the Modules
Follow these steps to mount the IAM, AM, SM, and SF modules. All modules 
mount to the power rail using the same technique. 
1. Determine the next available slot and module for mounting.
2. Insert the module in the power rail slot.
a. Align the module locking screw with its corresponding slot on the
power rail.
b. Push the module straight forward, by applying force at the top and
bottom of the front cover.
IMPORTANT
Invalid module positioning on a 2093-PRS8S power rail may result in 
incorrect operation. 
IMPORTANT
The IAM must be positioned in the leftmost slot of the power 
rail. Position your axis modules, shunt module, and slot fillers to 
the right of the IAM. 
ATTENTION
To avoid damage to the pins located on the back of each module 
(IAM, AM, SM, and SF) and to make sure that module pins mate 
properly with the power rail, install modules as shown below. 
The power rail must be mounted with the connectors in an 
upright or vertical orientation to the panel. This provides proper 
cooling of the modules. Do not mount modules if the power rail 
is not within three degrees of vertical.