Ungrounded Three-phase Power Configurations
Ungrounded power configurations are allowed, but you must jumper across a 
resistor (internal to the IAM) to prevent high electrostatic build-up. The 
ungrounded power configuration (shown below) does not provide a neutral 
ground point. The IAM has a ground jumper set for grounded power 
distribution (default configuration). 
Ungrounded Three-phase Power Configuration (delta secondary)
IMPORTANT
If you determine that you have ungrounded power distribution in your 
facility, you need to move the default jumper (configured for grounded 
power) to the ungrounded power position to prevent electrostatic 
buildup inside the IAM. 
Refer to the Setting the Ground Jumper in Ungrounded Power 
Configurations on page 69 for more information.
ATTENTION
Ungrounded systems do not reference each phase potential to a 
power distribution ground. This can result in an unknown potential to 
earth ground. 
L1
L2
L3
Integrated Axis Module, Front View
(2093-AC
xx
-MP
x
)
Conduit/4-Wire Cable
3-Phase
Input VAC
Ground
To Power Rail Ground Stud
Bonded Cabinet
Ground
Transformer
Internal Jumper Must Be Changed
For This Configuration