Minimizing Electrical 
Noise
This section outlines best practices which minimize the possibility of 
noise-related failures as they apply specifically to Kinetix 2000 system 
installations. 
For more information on the concept of high-frequency (HF) bonding, the 
ground plane principle, and electrical noise reduction, refer to the System 
Design for Control of Electrical Noise Reference Manual, publication 
GMC-RM001.
Bonding Modules
Bonding is the practice of connecting metal chassis, assemblies, frames, 
shields, and enclosures to reduce the effects of electromagnetic interference 
(EMI). 
Unless specified, most paints are not conductive and act as insulators. To 
achieve a good bond between power rail and the subpanel, surfaces need to be 
paint-free or plated. Bonding metal surfaces creates a low-impedance return 
path for high-frequency energy.
Improper bonding blocks the direct return path and results in high-frequency 
energy traveling elsewhere in the cabinet. Excessive high-frequency energy can 
effect the operation of other microprocessor controlled equipment. 
The illustrations that follow show details of recommended bonding practices 
for painted panels, enclosures, and mounting brackets. 
IMPORTANT
To improve the bond between the power rail and subpanel, construct 
your subpanel out of zinc plated (paint-free) steel.