SA3100 Drive Configuration and Programming

FEEDBACK REGISTERS (CONTINUED)

A/B

202/1202 Drive Fault

Bit
0 DC bus overvoltage fault

FLT_OV@

1 DC bus overcurrent fault

FLT_DCI@

2 Ground current fault

FLT_GND@

3 Instantaneous overcurrent

FLT_IOC@

4 Power supply fault

FLT_PWR@

6 Charge bus time-out fault

FLT_CHG@

7 Over temperature fault

FLT_OT@

8 Resolver broken wire fault

FLT_TBW@

9 Resolver fault

FLT_RES@

10 Over speed fault

FLT_OSP@

11 Power technology fault

FLT_PTM@

13 PMI bus fault

FLT_BUS@

14 UDC run fault

FLT_RUN@

15 Communication lost fault

FLT_COM@

203/1203 Drive Warning

Bit
0 DC bus overvoltage warning

WRN_OV@

1 DC bus undervoltage warning WRN_UV@
2 Ground current warning

WRN_GND@

3 Voltage ripple warning

WRN_VR@

4 Reference in limit warning

WRN_RIL@

5 Tuning aborted warning

WRN_TUN@

7 Over temperature warning

WRN_OT@

8 Bad gain data warning

WRN_BGD@

9 Thermistor open warning

WRN_TOC@

11 <reserved>
13 Flex I/O comm. warning

WRN_FLX@

14 CCLK not synchronized

WRN_CLK@

15 PMI communication warning WRN_COM@

204/1204 Power Device Status

Bit
0 Phase U -upper IOC A

U_UPA@

1 Phase V -upper IOC A

V_UPA@

2 Phase W-upper IOC A

W_UPA@

3 Phase U-lower IOC A

U_LOA@

4 Phase V-lower IOC A

V_LOA@

5 Phase W-lower IOC A

W_LOA@

6 Inverter Power Device Fault

IPMA@

205/1205 Interlock

Bit
0 Configuration not loaded

IC_CNF@

1 Valid gains not loaded

IC_GAIN@

2 Run permissive missing

IC_RPI@

3 Faults need reset

IC_FLT@

4 Rising edge required

IC_RISE@

5 More than one request

IC_MORE@

6 Bus not ready

IC_BUS@

7 MCR did not close

IC_MCR@

10 Incompatible resolver

IC_IRES@

FEEDBACK REGISTERS (CONTINUED)

Drive Data

A/B

206/1206 DC bus voltage (volts)

BUS_VDC%

207/1207 DC bus current (amps * 10) BUS_IDC%
208/1208 Ground current (amps * 10) GI_FB%
209/1209 Voltage feedback (Vrms)

V_FB%

210/1210 Current feedback (Irms * 10) I_FB%
211/1211 Volt command

V_CMD%

212/1212 Output frequency (high)

F_CMD(H)!

213/1213 Output frequency (low)

F_CMD(L)!

214/1214 User analog input

ANA_IN%

(-2048 = -10V to 2047 = 10V)
215/1215 Resolver Scan Position

RES_SCN_POS%

(-32768 to 32767)
216/1216 Current fdback normalized

I_FBN%

217/1217 Motor speed feedback (RPM)RPM%

Id feedback (dual-wound mtr)ID_FBK%

218/1218 Carrier frequency

F_CARR%

Vector orient ref (dl-wnd mtr) VO_FBK%

219/1219 Selected variable

SEL_VAR%

220/1220 Not used
221/1221 Not used
222/1222 Diagnostic fault code

DIAG_FLT%

300 - 599 Application registers updated every scan - A/B

UDC MODULE TEST INPUTS

1000

Switches
Bit
0 UDC pushbutton

UDC_PB@

1 UDC switch UP position

SWIT_UP@

2 UDC switch DOWN position

SWIT_DN@

LEDs
8 OS OK
9 Comm A OK
10 Drive A status
11 Comm B OK
12 Drive B status

METER PORT SETUP

1001

Initiate change in setup (non-zero value)

1002

Port 1 UDC register number (0-2047)

1003

Port 1 bit number (100-115, 0 = all bits)

1004

Port 1 maximum value

1005

Port 1 minimum value

1006

Port 2 UDC register number (0-2047)

1007

Port 2 bit number (100-115, 0 = all bits)

1008

Port 2 maximum value

1009

Port 2 minimum value

1010

Port 3 UDC register number (0-2047)

1011

Port 3 bit number (100-115, 0 = all bits)

1012

Port 3 maximum value

1013

Port 3 minimum value

1014

Port 4 UDC register number (0-2047)

1015

Port 4 bit number (100-115, 0 = all bits)

1016

Port 4 maximum value

1017

Port 4 minimum value

APPLICATION REGISTERS

1300 -

Application registers updated every

1599

Nth scan - A/B

INTERRUPT STATUS AND CONTROL (ISCR)

2000

Interrupt status and control

UDC_ISCR%

Bit
0 Interrupt line ID
2 Interrupt allocated
4 Interrupt generated this scan
5 CCLK counting
6 Enable CCLK to backplane*
7 Interrupt enabled
15 Interrupt status
* Only bit 6 in register 2000 can be written to by

the programmer. All other bits in register 2000
are read only.

2001

Scans per interrupt

LOCAL TUNABLE VARIABLES

Current minor loop crossover

CML_WCO%

frequency (1 = 1 radian/sec)
Ground current warning threshold

GIT_E1%

(10 = 1 amp)
Over voltage warning threshold

OVT_E0%

(1 = 1 volt)
Power loss fault threshold

PLT_E0%

(1 = 1 volt)
Resolver balance

RES_BAL%

(Default CURRENT value = 0)
Resolver gain

RES_GAN%

(Default CURRENT value = 0)
Under voltage warning threshold

UVT_E0%

(1 = 1 volt)
Voltage ripple warning threshold

VRT_E0%

(1 = 1 volt)

VOLTAGE POINT TUNABLE GAINS (1000 = 1 volt)

Point 0 Voltage

P0VT_E3!

Point 1 Voltage

P1VT_E3!

Point 2 Voltage

P2VT_E3!

Point 3 Voltage

P3VT_E3!

Point 4 Voltage

P4VT_E3!

Point 5 Voltage

P5VT_E3!

Point 6 Voltage

P6VT_E3!

FREQUENCY POINT TUNABLE GAINS (1000 = 1 Hz)

Point 0 Frequency

P0HZ_E3!

Point 1 Frequency

P1HZ_E3!

Point 2 Frequency

P0HZ_E3!

Point 3 Frequency

P3HZ_E3!

Point 4 Frequency

P4HZ_E3!

Point 5 Frequency

P5HZ_E3!

Point 6 Frequency

P6HZ_E3!