Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual

Page 125

Advertising
background image

SA3100 Local Tunable Variables

C-3

Tuning STATOR_IZ_E1% for Constant Power Applications

The SA3100 Constant Power operating system has the capability of
accommodating temperature changes via modification of the slip value. This
modification of the slip value is accomplished through the use of a PMI reference
magnetizing current table, which enables the PMI to determine when a load change
has occurred.

When a load change occurs, the output of the flux loop will increase. This increased
output is compared to the value from the reference table. The difference between
the two generates a change in slip. The change in slip causes a reduction in flux
loop output which, in turn, causes the flux loop output to be the correct value for the
magnetizing current value at that point in the speed range.

In order to tune or calibrate the table, a speed loop is implemented in the UDC
module. This speed loop must be set up so that a value of 4095 counts of speed
reference corresponds to the maximum speed of the drive (i.e. four times the
maximum voltage speed). The following table indicates the speed reference points
at which data is to be obtained: Note that the values saved in the IGNn! variables
will be in units of amps

100.

Ref. Point

Speed Reference

Counts

Where the Value is

Saved

One

409

STATOR_IZ_E1%

Two

1023

1

1. Equal to maximum voltage speed.

The number of reference points required depends upon the
speed range of the application:

For a 2 to 1 range, reference points 1 to 7 are used.

For a 3 to 1 range, reference points 1 to 9 are used.

For a 4 to 1 range, reference points 1 to 10 are used.

IGN1!

Three

1125

IGN2!

Four

1227

IGN3!

Five

1329

IGN4!

Six

1635

IGN5!

Seven

1941

IGN6!

Eight

2247

IGN7!

Nine

2859

IGN8!

Ten

4095

IGN9!

STATOR_IZ_E1%

No Load Stator Current