Run Time AC Power Technology Hardware Faults (Continued):

DC Bus Pre-charge Faults:

Diagnostic Fault Code Register (Continued)

222/1222

Code

Fault

Description/Action

22

A/D interrupt overrun

An interrupt from the power technology
circuit was detected before the previous
interrupt was processed. Replace the
PMI Regulator motherboard.

23

Gate power test 1 fault

Gate power is on when the MCR is off
and Gate Enable is on. Replace the PMI
Regulator motherboard.

24

Not used.

25

Gate power test 3 fault

Gate power is on when the MCR is off
and Gate Enable is on. Replace the PMI
Regulator motherboard.

26

Gate power loss

Loss of gate power feedback while in
run. Replace the PMI Regulator
motherboard.

Code

Fault

Description/Action

100

Pre-charge closed

Pre-charge is requested to close when
Pre-charge is already closed.

101

Pre-charge did not close

The pre-charge did not close within 2
seconds.

102

Pre-charge open

Pre-charge is closed but AC power
technology status indicates it is open.

103

Pre-charge did not open

Pre-charge is commanded to open but
does not do so after one second.

104

Pre-charge opened

The AC power technology circuit
detected that the pre-charge opened
while in run.

105

No used

106

Charge time-out

Minimum bus voltage is not detected
within 10 seconds after bus enable.

107

AC line fault

AC line status from Power Module not
detected.

108

Charge ripple fault

DC ripple voltage above tolerance.

200

Diag_12V PS

Isolated 12V power supply is out of
tolerance.

201

Diag_PS_Ext_PS

External ±15V power supply (for G or
H-frame units) is out of tolerance.