Configuring the UDC Module’s Registers

3-55

3.7.2 UDC Module Meter Port Setup Registers (Registers 1000-1017)

Registers 1001-1017 are used to configure the UDC module’s meter ports. This
configuration determines what variables from the UDC module’s dual port memory are
to be displayed on the meter ports at the end of the UDC scan. At system power-up,
the output values of the ports are reset to zero.

To map a UDC variable to a specific meter port at power-up, refer to table 3.8 and use
the following procedure. Note that the setup register configurations are retained
during a Stop All.

For each meter port:

Step 1. Place the register number of the variable you wish to display in the

appropriate Variable Register Number register.

Step 2. If an individual bit of the register is to be displayed, enter it in the Bit Number

register as 100 (bit 00) to 115 (bit 15).

Step 3. Place the value (maximum 32767) that will represent +10V in the Maximum

Value register.

Step 4. Place the value (minimum -32768) that will represent -10V in the Minimum

Value register.

Step 5. Set register 1001 (Initiate Change in Setup) equal to a non-zero value to

store the new setup register configurations in memory.

The UDC module’s meter ports are updated once per scan once the UDC task is
running and CCLK is on. They are updated every 5 milliseconds when CCLK is off.

UDC meter ports can also be set up on-line using the “Setup UDC” selection from the
Monitor menu as described in the AutoMax Programming Executive instruction
manual. This setup is valid only until there is a power cycle, in which case the meter
ports default to outputting zero voltage and the UDC Setup screen is cleared on
power-up.

Refer to the UDC module instruction manual (S-3007) for more information about the
UDC module’s meter ports.

Table 3.8 – UDC Module Meter Port Setup Registers

UDC Module Meter Port
Setup Registers

Meter

Port 1

Meter

Port 2

Meter

Port 3

Meter

Port 4

Change Setup Register

1001

1001

1001

1001

Variable Register Number Register

1002

1006

1010

1014

Bit Number Register

1003

1007

1011

1015

Maximum Value Register

1004

1008

1012

1016

Minimum Value Register

1005

1009

1013

1017