Configuring the UDC Module’s Registers

3-57

Meter Port 1

UDC Module Meter Port 1 Register Number Register

1002

UDC register number (0 - 2044) to be mapped to meter port 1.

Sug. Var. Name:

N/A

Units:

N/A

Range:

N/A

Access:

Read/Write

UDC Module Meter Port 1 Bit Number Register

1003

Bit number of the UDC register specified in register 1002 that is to be
mapped to port 1. Enter a value of 100 (bit 00) to 115 (bit 15) as
required. Enter a value of zero if all of the register’s bits are to be
displayed.

Sug. Var. Name:

N/A

Units:

N/A

Range:

N/A

Access:

Read/Write

UDC Module Meter Port 1 Maximum Value Register

1004

Set this register to the number that will represent +10V. The
maximum allowable value is 32767.

Sug. Var. Name:

N/A

Units:

N/A

Range:

N/A

Access:

Read/Write

UDC Module Meter Port 1 Minimum Value Register

1005

Set this register equal to the number that will represent -10V. The
minimum allowable value is -32768.

Sug. Var. Name:

N/A

Units:

N/A

Range:

N/A

Access:

Read/Write