Configuring the UDC Module’s Registers

3-15

PMI Communication Status Register (Continued)

84/1084

Overrun Error

Bit 3

The Overrun Error bit is set if the USC
reports a receive first-in, first-out overrun.

Hex Value:

0008H

Sug. Var. Name:

N/A

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

DMA Format Error

Bit 4

The DMA Format Error bit is set if the length
of the received message does not match the
length encoded in the message itself.

Hex Value:

0010H

Sug. Var. Name:

N/A

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

Transmitter Underrun

Bit 5

The Transmitter Underrun bit is set if the
USC reports a transmit first-in, first-out
underrun.

Hex Value:

0020H

Sug. Var. Name:

N/A

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

CCLK Communication Synchronization Error

Bit 6

The CCLK Communication Synchronization
Error bit is set if two or more CCLK counter
ticks occur and no message is received.

Hex Value:

0040H

Sug. Var. Name:

N/A

Access:

Read only

Sug. Var. Name:

VDC_RUN@

UDC Error Code:

N/A

LED:

N/A

UDC CCLK Communication Synchronization Error

Bit 8

The UDC CCLK Communication
Synchronization Error bit is set if two UDC
CCLK counter ticks occur and no message
is received from the PMI.

Hex Value:

0100H

Sug. Var. Name:

N/A

Access:

Read only

UDC Error Code:

N/A

LED:

N/A