Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual
Page 86

3-48
SA3100 Drive Configuration and Programming
AC Power Technology Calibration and Power-Up Faults:
If any of the following calibration and power-up diagnostic faults occurs, replace the
PMI Regulator motherboard. These faults indicate a hardware failure of the AC power
technology circuit on the motherboard. Register 202, bit 11 (FLT_PTM@) will be set.
Run Time AC Power Technology Hardware Faults:
Diagnostic Fault Code Register
222/1222
The Diagnostic Fault Code register displays an error code to help
diagnose the cause of a problem reported in other registers.
Note that this register is available for monitoring only. It cannot be
referenced in an application task.
Sug. Var. Name:
DIAG_FLT%
Units:
N/A
Range:
N/A
Access:
Read only
Code
Fault
1
D/A high voltage error (+3.3V 10% out of tolerance)
2
D/A low voltage error (-3.3V 10% out of tolerance)
3
Torque current loop proportional gain not within calibration limits
(14<g<30)
4
Flux current loop proportional gain not within calibration limits (14<g<30)
5
Flux current loop integrator time constant not within calibrated limits
6
Torque current loop integrator time constant not within calibrated limits
7
Modulation index error
8
Harmonic DAC limit error
9
Modulation range error
10
Harmonic DAC range error
11
Programmable current limit or the ground fault limit fault
12
Voltage feedback integrator error
13
A/D converter interrupt error
14
Pulse Width Modulator frequency error
15
DC bus current not zero at power-up.
16
Phase U current not zero at power-up.
17
Phase W current not zero at power-up.
Code
Fault
Description/Action
20
Power supply monitor trip
AC power technology power supply level
out of tolerance. Replace the PMI
Regulator motherboard and/or power
supply.
21
AC power technology
watchdog time-out
AC power technology circuit watchdog
timer expired. Replace the PMI
Regulator motherboard.