SA3100 Drive Configuration and Programming

Drive Fault Register (Continued)

202/1202

Communication Lost Fault

Bit 15

The Communication Lost Fault bit is set if
the fiber-optic communication between the
PMI Processor and the UDC module is lost
due to two consecutive errors of any type.

Hex Value:

8000H

Sug. Var. Name:

FLT_COM@

Access:

Read only

UDC Error Code:

1015

LED:

COMM OK

This bit is set only after communication between the PMI Regulator and UDC
module has been established. This bit should be used in the run permissive logic for
the drive. Also refer to the CCLK Synchronized bit (register 200/1200, bit 14).

Drive Warning Register

203/1203

The warnings indicated by the Drive Warning register cause no action by themselves. Any resulting action is
determined by the application task. The user must ensure that the AutoMax application task monitors
register 203/1203 and takes appropriate action if any of these conditions occurs. If a warning condition is
detected, the corresponding bit is latched until the Warning Reset bit (bit 9) of the Drive Control register
(register 100/1100) is set.

DC Bus Overvoltage Warning

Bit 0

The DC Bus Overvoltage Warning bit is set
if the DC bus voltage rises above the
overvoltage threshold value stored in local
tunable OVT_E0%.

Hex Value:

0001H

Sug. Var. Name:

WRN_OV@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

The torque is automatically limited to avoid an overvoltage fault. Bit 4 of the Drive
Warning register will also be set to indicate the torque is being limited by the
system. Refer to the SA3100 Power Modules instruction manual (S-3058) for more
information about internal DC bus control.

DC Bus Undervoltage Warning

Bit 1

The DC Bus Undervoltage Warning bit is set
if the DC bus voltage drops below the
undervoltage threshold stored in local
tunable UVT_E0%.

Hex Value:

0002H

Sug. Var. Name:

WRN_UV@

Access:

Read only

UDC Error Code:

N/A

LED:

N/A

The torque is automatically limited to avoid an undervoltage fault. Bit 4 of the Drive
Warning register will also be set to indicate the torque is being limited by the
system. Refer to the SA3100 Power Modules instruction manual (S-3058) for more
information about internal DC bus control.