SA3100 Drive Configuration and Programming

C.4 Volts per Hertz Frequency Point Gain Variables

These seven gains below represent the seven frequency points of the V/Hz
characteristic curve. Output voltage varies with output frequency according to the
V/Hz characteristic.

When the enable tuning command (register 100/1100, bit 1, PMI_TUN@) is asserted,
these gains are reset to their default values. When the reset is complete register 200,
bit 1 (PMI_ATC@) is set

See Appendix E (Figures E.2 and E.3) for more information on the V/Hz characteristic.

P5VT_E3!

Point 5 Voltage

This value is set to select the voltage at point 5
in the V/Hz characteristic curve.

This value is entered in times 1000, e.g., 50
volts is entered as 50000.

Units:

Volts

1000

Default Value:

0

Low Limit:

0

High Limit:

1000000

Step:

1

P6VT_E3!

Point 6 Voltage

This value is set to select the voltage at point 6
in the V/Hz characteristic curve.

This value is entered in times 1000, e.g., 50
volts is entered as 50000.

Units:

Volts

1000

Default Value:

0

Low Limit:

0

High Limit:

1000000

Step:

1

P0HZ_E3!

Point 0 Frequency

This value is set to select the frequency at
point 0 in the V/Hz characteristic curve.

Note that P0HZ_E3 is always 0 (zero) Hz.

Units:

Hz

1000

Default Value:

0

Low Limit:

0

High Limit:

0

Step:

0