Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual

Page 151

Advertising
background image

J-4

Drive Configuration and Programming

For a 2 to 1 range; reference points one, two, three, four, five, six and seven are
used.

For a 3 to 1 range; reference points eight and nine are also used.

For a 4 to 1 range; reference point ten is also used.

Note that PMI operating system version requires internal gain tunables IGN1! to
IGN9! for retention of the table data.

(IGN ==> Internal Gain)

Use the following procedure to implement each reference point in the speed loop
calculation:

Step 1. With the drive’s motor unconnected, set bits 0 and 1 of register 101/1101.

Register 101 is for Drive A and register 1101 is for Drive B. Drive B can be
setup by using the register number for Drive A plus 1000.

The following steps will use Drive A for this example.

Step 2. Command the speed loop to the appropriate speed reference.

Step 3. When the speed is reached, set bit 10 of register 101 in the UDC.

Step 4. Monitor register 203 and bit 10 of register 201.

Step 5. If register 203 is set to hex 20, reset bit 10 of register 101 and go to step 7.

Step 6. If bit 10 of register 201 was set, reset bit 10 in register 101 and continue with

the next speed point as described in step 3. When all the required speed
points have been completed, go to step 8.

Step 7. If register 203 contains a hex value of 20, verify that the speed scaling of the

speed loop is correct and refer to the Notes at the end of this appendix. Reset
the warning, and continue with the next speed point as described in step 3.

Step 8. Reset bits 0 and 1 of register 101.

Note: The values saved in the IGNn! variables will be in (amps*100) units.

Note that in Dual Wound Motor Applications (Parallel Inverter Drives) you must
use the procedure described above with the following additions:

• After using the reference point data for Drive A (register 101), use the

reference point data for Drive B register (1101).

• Ensure that the vector orientation alignment request bit (bit 6, 0040h) is set in

register 1100.

• The IGNn! values for the A and B drives should be the same. The acquisition

of data should be done with both drives to verify that the magnitudes of the
values are similar. After the acquisition is done, the IGNn! values from Drive
A should be used for Drive B.

Advertising