3 flex i/o status and error codes, 3 flex i/o status and error codes -9 – Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual

Page 47

Advertising
background image

Configuring the UDC Module’s Registers

3-9

3.2.3 Flex I/O Status and Error Codes

Register 10/22 contains status and error codes for Flex I/O Module 0 and Module 1.
The memory map is shown in table 3.6.

Table 3.6 – Register 10/22 - Flex I/O Module 0 and Module 1 Faults

Bit

Name

Description

0

Flex Bus Fault

Set if the Flex Bus Interface on the PMI Regulator has faulted.

1

Flex Clock Warning

Set if the Flex I/O clock is not running.

2

Flex Scratch Pad Warning

Set if a read/write Flex I/O memory error is detected.

3

Flex Dual Port Warning

Set if a read/write Flex I/O dual port memory error is detected.

8

Module 0 Not Plugged In

Set if no device is detected at the Module 0 port.

9

Module 0 Communication Error

Set if there is a serial communication error with Module 0.

10

Module 0 Bad ID

Set if a non-supported module ID is received from Module 0 or if
the module ID received does not match the configured ID.

11

Module 0 Location Error

Set if an analog module is physically located in the Flex I/O rail
location designated for Module 0, and Module 0 has been
configured for a Digital module.

12

Module 1 Not Plugged In

Set if no device is detected at the Module 1 port.

13

Module 1 Communication Error

Set if there is a serial communication error with Module 1.

14

Module 1 Bad ID

Set if a non-supported module ID is received from Module 1 or if
the module ID received does not match the configured module
ID.

15

Module 1 Location Error

Set if an analog module is physically located in the Flex I/O rail
location designated for Module 0 or Module 1, and Module 1 has
been configured for a Digital module.