Page 36

2-24
SA3100 Drive Configuration and Programming
2.5
Configuring Flex I/O
The Configure Flex I/O Parameter Entry Screen allows you to configure your Flex I/O
Modules, if Flex I/O is being used with your system. See figure 2.14.
A maximum of three Flex I/O modules is allowed. Module 0 and Module 1 must be
digital; Module 2 can be either digital or analog.
•
Module 0
Select a digital I/O module from the pull-down list. Only the supported digital I/O
modules will be displayed. There is no default selection. You must choose a module
from the list.
•
Module 1
Select a digital I/O module from the pull-down list. Only the supported digital I/O
modules will be displayed. There is no default selection. You must choose a module
from the list.
•
Module 2
Select an analog or digital I/O module from the pull-down list of supported modules.
There is no default selection. You must choose a module from the list.
•
Filter Time
This parameter is used only with input modules. The system determines the default
filter time for the module selected. You may select a different time from a pull-down
list.
Figure 2.14 – Flex I/O Parameter Entry Screen