C.5 DC Bus Variables

The programmer selects the values in the following variables to determine the drive’s
response to changes in the DC bus. Note that the following relationship must be true
or a drive warning will occur (register 203/1203, bit 8):

PLT_E0% < UVT_E0% < OVT_E0%

For more information about internal DC bus control, refer to the SA3100 Power
Modules instruction manual (S-3058).

OVT_E0%

Over Voltage Warning Threshold

A drive warning is generated (203/1203, bit 0) if
DC bus voltage exceeds the value stored in this
variable. It should be set below the hardware
over voltage fault limit and above the normal
operating voltage. The value is entered in volts.

Units:

Volts

Default Value:

300

Low Limit:

300

High Limit:

1000

Step:

1

The hardware over voltage fault limit is 400V for 230V Power Modules, 800V for
460V Power Modules, and 975V for 575V Power Modules. The normal operating
voltage is displayed in the DC Bus Voltage Feedback register (206/1206).

This value also selects the starting point at which the system begins reducing the
regeneration torque limit. Bit 4 of the Drive Warning register (203/1203) is also set
to indicate the system is limiting torque.

PLT_E0%

Power Loss Fault Threshold

A drive fault is generated (202/1202, bit 6) if DC
bus voltage drops below the value stored in this
variable.

Units:

Volts

Default Value:

250

Low Limit:

250

High Limit:

825

Step:

1

This value should be set to 100V below the normal operating voltage of the bus. It is
entered in volts. The normal operating voltage of the bus is displayed in the DC Bus
Voltage Feedback register (206/1206).

When deciding what value to use for PLT_E0%, note that the instantaneous change
in voltage on the bus capacitors in the Power Module cannot exceed 100V.

UVT_E0%

Undervoltage Warning Threshold

A drive warning is generated (register 203,
bit 1) if DC bus voltage is less than the value
stored in this variable. This value should be set
above the value selected for the Power Loss
Fault Threshold variable. It is entered in volts.

Units:

Volts

Default Value:

250

Low Limit:

250

High Limit:

825

Step:

1