Configuring the UDC Module’s Registers
3-41
Power Device Status Register (Continued)
204/1204
Inverter Power Device Fault
Bit 6
The Inverter Power Device Fault bit is set if
the gate driver turns off an output power
device (IGBT) to protect it from an
overcurrent.
Bit 3 in register 202 will also be set.
Hex Value:
0040H
Sug. Var. Name:
IPMA@
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
If an output short circuit occurs, a high current will flow in the IGBT causing its
collector-to-emitter voltage to increase to a level much higher than normal. The
gate driver detects this condition and instantly shuts off the IGBT to prevent its
destruction.
Bit 7
Reserved for future use.
Hex Value:
0080H
Sug. Var. Name:
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Bit 8
Reserved for future use.
Hex Value:
0100H
Sug. Var. Name:
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Bit 12
Reserved for future use.
Hex Value:
1000H
Sug. Var. Name:
Access:
Read only
UDC Error Code:
N/A
LED:
N/A
Bit 13
Reserved for future use.
.
Hex Value:
2000H
Sug. Var. Name:
Access:
Read only
UDC Error Code:
N/A
LED:
N/A