3-46

SA3100 Drive Configuration and Programming

Iq Feedback Normalized Register (Vector)

213/1213

In Vector mode, register 213/1213 functions as Iq Feedback
Normalized register. This register contains the Iq (torque producing)
component of the current feedback. The data is normalized so that
+/- 4095 counts corresponds to the torque reference (TRQ_REF%).

Sug. Var. Name:

IQ_FBN%

Units:

Counts

Range:

+/- 4095

Access:

Read only

Output Frequency Register (V/Hz)

212/1212 and 213/1213

In Volts per Hertz mode, registers 212/1212 and 213/1213 function
as the Output Frequency register. This double precision register
contains the output frequency value of the drive. Register 212/1212
holds the high word. Register 213/1213 holds the low word. The
value is scaled in Hz

1000.

Sug. Var. Name:

F_CMD!

Units:

Hz

1000

Range:

0 to 600,000

Access:

Read only

User Analog Input Register

214/1214

The User Analog Input register contains the measured user analog
input value from the Resolver Feedback connector on the Resolver &
Drive I/O board.

Sug. Var. Name:

ANA_IN%

Units:

Counts (Volts)

Range:

-2048 to +2047

(-10V to +10V)

Access:

Read only

Resolver Scan Position Register

215/1215

The Resolver Scan Position register contains the electrical position of
the resolver at the beginning of the UDC task scan. This register is
reset to zero at power-up.

Sug. V ar. Name: RES_SCN_POS%
Units:

Counts

Range:

-32768 to +32767

Access:

Read only

Resolver Strobe Position Register

216/1216

The Resolver Strobe Position register contains the electrical position
of the resolver at the time a strobe signal is detected.

Sug. Var. Name: RES_STR_POS%
Units:

Counts

Range:

-32768 to +32767

Access:

Read only

Current Feedback Normalized Register (V/Hz)

216/1216

In Volts per Hertz mode, register 216/1216 functions as the Current
Feedback Normalized register. This register contains the measured
RMS motor current. The data is normalized so that +/- 4095 counts is
equal to the rated motor current times the motor overload ratio.

Sug. Var. Name:

I_FBN%

Units:

Counts

Range:

+/- 4095

Access:

Read only

This register is used as the I_FDBK parameter in the THERMAL OVERLOAD control block used in DPS
drives to monitor the motor for thermal overload.

Note that the regulator uses a value of 150% overload for this function. If another value of overload ratio is
desired, it must be communicated to the regulator via the dual port register 711/1711.