Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual

Page 37

Advertising
background image

Configuring the UDC Module, Regulator Type, and Parameters

2-25

Channel 0 to Channel 7

If an analog I/O module is selected for Module 2, you must configure the channels
for the analog module appropriately. No error checking is done by the system. The
channels all default to “not used”.

2.6

Generating Drive Parameter Files
and Printing Drive Parameters

When you have completed all of the drive parameter screens, you can select “Close”
to leave the Parameter Entry Screens and return to the master rack diagram with the
UDC module selected. Zoom out or select the Exit command from the Configure menu
to return to the System Configurator.

You can generate the drive parameter files by using the steps that follow.

Step 1. From the System Configurator, access the Task Manager by selecting the

Manage Tasks command from the Rack menu.

Step 2. Select the Generate Configuration command from the Commands menu.

Step 3. Check the Generate Drive Parameter Files option in the Generate Files

dialog box, and then select OK.

A file containing the newly-entered drive parameters will be created. The file
will be named PARAMxx.POB, where xx is the slot number of the UDC
module. Note that the drive parameter files must be loaded to the rack before
(or at the same time as) the UDC application tasks are loaded to the rack.
Refer to the AutoMax Programming Executive instruction manual for more
detailed information.

You can print the drive parameters for a UDC module you specify by using
the Print command from the Rack menu in the System Configurator. Refer to
the AutoMax Programming Executive instruction manual for step-by-step
instructions.

Advertising