SA3100 Local Tunable Variables

C-7

P1HZ_E3!

Point 1 Frequency

This value is set to select the frequency at
point 1 in the V/Hz characteristic curve.

This value is entered in hertz times 1000, e.g.,
60 hertz is entered as 60000.

Units:

Hz

1000

Default Value:

0

Low Limit:

0

High Limit:

660000

Step:

1

P2HZ_E3!

Point 2 Frequency

This value is set to select the frequency at
point 2 in the V/Hz characteristic curve.

This value is entered in hertz times 1000, e.g.,
60 hertz is entered as 60000.

Units:

Hz

1000

Default Value:

0

Low Limit:

0

High Limit:

660000

Step:

1

P3HZ_E3!

Point 3 Frequency

This value is set to select the frequency at
point 3 in the V/Hz characteristic curve.

This value is entered in hertz times 1000, e.g.,
60 hertz is entered as 60000.

Units:

Hz

1000

Default Value:

0

Low Limit:

0

High Limit:

660000

Step:

1

P4HZ_E3!

Point 4 Frequency

This value is set to select the frequency at
point 4 in the V/Hz characteristic curve.

This value is entered in hertz times 1000, e.g.,
60 hertz is entered as 60000.

Units:

Hz

1000

Default Value:

0

Low Limit:

0

High Limit:

660000

Step:

1

P5HZ_E3!

Point 5 Frequency

This value is set to select the frequency at
point 5 in the V/Hz characteristic curve.

This value is entered in hertz times 1000, e.g.,
60 hertz is entered as 60000.

Units:

Hz

1000

Default Value:

0

Low Limit:

0

High Limit:

660000

Step:

1

P6HZ_E3!

Point 6 Frequency

This value is set to select the frequency at
point 6 in the V/Hz characteristic curve.

This value is entered in hertz times 1000, e.g.,
60 hertz is entered as 60000.

Units:

Hz

1000

Default Value:

0

Low Limit:

0

High Limit:

660000

Step:

1