Chapter 3 configuring the udc module’s registers, Chapter 3, Conf – Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual

Page 39: Hapter, Configuring the udc module’s registers

Advertising
background image

Configuring the UDC Module’s Registers

3-1

C

HAPTER

3

Configuring the UDC Module’s

Registers

The Variable Configurator application in the AutoMax Programming Executive is used
to assign common variable names to the dual port memory registers on the UDC
module. You can access these variable names by declaring them using the BASIC
statement COMMON. The dual port memory has 2048 16-bit registers that are
available to the AutoMax Processor and to the tasks that run on the UDC module.

The drive A and drive B registers that are assigned variable names will be latched into
internal memory at the beginning of every scan of the UDC task to provide for a
consistent context for evaluation. The UDC tasks (A and B) may be started and
stopped independently of each other. At the end of the scan, the variables that have
changed will be written back to the dual port memory.

Note that the dual port memory on the UDC module is treated like I/O data in terms of
how the data is affected by Stop All commands and power cycling.

You can access the Variable Configurator by selecting Configure Variables from the
Configure menu in the Rack Configurator. Refer to the AutoMax Programming
Executive instruction manual for the procedures used to configure variables.

The sections that follow describe the registers you can configure in each view:

The Port 0 Flex I/O Rail view is used to configure the registers assigned to the
hardware that is attached to the PMI Flex I/O port. (These registers can also be
accessed by double-clicking the PMI view.)

!

ATTENTION:Only qualified electrical personnel familiar with the
construction and operation of this equipment and the hazards involved
should install, adjust, operate, or service this equipment. Read and
understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in
severe bodily injury or loss of life.

ATTENTION:Only qualified Drive Systems personnel or other trained
personnel who understand the potential hazards involved may make
modifications to the variable configuration. Any modifications may result
in uncontrolled machine operation. Failure to observe this precaution
could result in damage to equipment and bodily injury.

ATTENTION:Registers and bits in the UDC module that are described
as “read only” or for “system use only” must not be written to by the user.
Writing to these registers and bits may result in improper system
operation. Failure to observe this precaution could result in bodily injury.

Advertising