Configuring the UDC Module’s Registers

3-35

Drive Fault Register (Continued)

202/1202

Overspeed Fault

Bit 10

The Overspeed Fault bit is set if the motor’s
velocity exceeds the value entered as the
Overspeed Trip (RPM) configuration
parameter.

Hex Value:

0400H

Sug. Var. Name:

FLT_OSP@

Access:

Read only

UDC Error Code:

1010

LED:

EXT FLT

Power Technology Fault

Bit 11

The Power Technology Fault bit is set to
indicate a problem with the AC power
technology circuit on the PMI Regulator
motherboard.

Hex Value:

0800H

Sug. Var. Name:

FLT_PTM@

Access:

Read only

UDC Error Code:

1011

LED:

OK

Register 222/1222 provides additional diagnostics if this fault occurs.

Bit 12

Reserved for future use.

Hex Value:

1000H

Sug. Var. Name:
Access:

Read only

UDC Error Code:

1012

LED:

PMI Regulator Bus Fault

Bit 13

The PMI Regulator Bus Fault bit is set if the
Resolver & Drive I/O board or the AC power
technology circuit does not respond to
requests from the PMI Processor. This
indicates a hardware problem in the PMI
Regulator.

Hex Value:

2000H

Sug. Var. Name:

FLT_BUS@

Access:

Read only

UDC Error Code:

1013

LED:

N/A

UDC Run Fault

Bit 14

The UDC Run Fault bit is set if the UDC task
stops while the minor loop is running in the
PMI Regulator.

Hex Value:

4000H

Sug. Var. Name:

FLT_RUN@

Access:

Read only

UDC Error Code:

1014

LED:

N/A