Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual

Page 48

Advertising
background image

3-10

SA3100 Drive Configuration and Programming

Register 11/23 contains status and error codes for Flex I/O Module 2. The memory
map is shown in table 3.7.

Table 3.7 – Register 11/23 - Flex I/O Module 2 Faults

Bit

Name

Description

0

Module 2 Not Plugged In

Set if no device is detected at Module 2 port.

1

Module 2 Communication Error

Set if there is a serial communication error with Module 2.

2

Module 2 Bad ID

Set if a non-supported module ID is received from Module 2 or if
the module ID received does not match the configured ID.

8

Channel 0 - Open Output/
Underrange Input

Bits 8 to 15 are set if there is an open output (4 - 20 mA current
output only) or an under range input (4 - 20 mA current input
only).

If a digital input is installed for Module 2 these bits are not used.

9

Channel 1 - Open Output/
Underrange Input

10

Channel 2 - Open Output/
Underrange Input

11

Channel 3 - Open Output/
Underrange Input

12

Channel 4 - Open Output/
Underrange Input

13

Channel 5 - Open Output/
Underrange Input

14

Channel 6 - Open Output/
Underrange Input

15

Channel 7 - Open Output/
Underrange Input