Rockwell Automation SA3100 Distributed Power System Drv Config,Program User Manual
Page 48

3-10
SA3100 Drive Configuration and Programming
Register 11/23 contains status and error codes for Flex I/O Module 2. The memory
map is shown in table 3.7.
Table 3.7 – Register 11/23 - Flex I/O Module 2 Faults
Bit
Name
Description
0
Module 2 Not Plugged In
Set if no device is detected at Module 2 port.
1
Module 2 Communication Error
Set if there is a serial communication error with Module 2.
2
Module 2 Bad ID
Set if a non-supported module ID is received from Module 2 or if
the module ID received does not match the configured ID.
8
Channel 0 - Open Output/
Underrange Input
Bits 8 to 15 are set if there is an open output (4 - 20 mA current
output only) or an under range input (4 - 20 mA current input
only).
If a digital input is installed for Module 2 these bits are not used.
9
Channel 1 - Open Output/
Underrange Input
10
Channel 2 - Open Output/
Underrange Input
11
Channel 3 - Open Output/
Underrange Input
12
Channel 4 - Open Output/
Underrange Input
13
Channel 5 - Open Output/
Underrange Input
14
Channel 6 - Open Output/
Underrange Input
15
Channel 7 - Open Output/
Underrange Input