Control i/o, The signal names and descriptions of each terminal, Matching connector specifications – KEYENCE LT-9001 Series User Manual

Page 117

Advertising
background image

7

Chapter

I/O

Terminal

E LT-9001-IM

7-3

The signal names and descriptions of each terminal

The signal names and descriptions of each terminal are described as follows.

Refer to "Functions of the I/O Signal" (page 7-5) for the detailed functions.

• 24V DC (–) and COM1 are common via a choke coil. Be careful not to generate

a potential difference.

• 0 V for the analog monitor output is isolated from COM1. It is common to the FG

terminal for the AC power supply.

• 24V DC terminal is a dedicated power supply terminal for the monitor specified

by KEYENCE ONLY. Do not use to power other external devices.

The control I/O can be selected from the binary output of the measured value or

the tolerance judgment output depending on the setting.

Refer to "I/O" (page 5-20) for the setting details.

Matching connector specifications

HIROSE Electric HIF3B Series or equivalent

The pin layout is as follows.

Control I/O

Note

Terminal number

Signal name

Description

1

MON1

Analog monitor output1

2

MON2

Analog monitor output2

3

0V

0 V for analog monitor output

4

ZERO

Auto-zero input

5

RESET

Reset input

6

TIMING

Timing input

7

COM1

COM for 4 to 6

8

24V DC (–)

Power (–) terminal for the monitor (CA-MN80)

9

24V DC (+)

Power (+) terminal for the monitor (CA-MN80)

17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18

Terminal number