5 communication time – KEYENCE BL-700 Series User Manual

Page 131

Advertising
background image

117

Chapter 6 PCL Link

6

6.5

Communication Time

Time required data transmission
The time required for data transmission from the BL-700 to the PLC is as follows:
This communication time may change depending on the PLC's scan time and the
model of the PLC.

* When the RS-232C communication baud rate is 9600 bps:

Communication time to start reading using reading trigger area
To control the BL series’ reading operation using the reading trigger area, enter the
trigger ON command on the PLC, and obtain the time duration until the command
is received by the BL-700.

* When the RS-232C communication baud rate is 9600 bps:

Number of data digits

MELSEC-A

SYSMAC-C

KV (KV mode)

10

Approx. 220 ms

Approx. 330 ms

Approx. 440 ms

20

Approx. 270 ms

Approx. 380 ms

Approx. 680 ms

32

Approx. 320 ms

Approx. 460 ms

Approx. 920 ms

MELSEC-A

SYSMAC-C

KV (KV mode)

Approx. 60 ms

Approx. 80 ms

Approx. 30 ms