SPECIFICATIONS

General specifications for the BE1-25A system are provided in the following paragraphs. For
specifications that apply only to particular options, see the ensuing subsection entitled Specifications of
Options.

Voltage Sensing Inputs

70 to 150 Vac, 50/60 Hz. Burden: Less than 6 VA for the generator

(Bus and Generator)

input; less than 2 VA for the bus input.

Contact Sensing Inputs

Requires a user-supplied contact with a minimum rating of 0.05 A at
250 Vdc.

Power Supply

Power for the internal circuitry may be derived from 90 to 132 Vac at
50/60 Hz (single phase), or 70 to 150 Vdc. Burden: Less than 20.0
VA.

Outputs

Output contacts are rated as follows:

Breaker Closing

Normally open. Make and carry 30 A at 250 Vdc for 1 second, 7 A

continuously, and break 0.3 A at 250 Vdc. (L/R = 0.04).


Voltage, Frequency (Speed) Correction, and Lockout

Form C (SPDT). Make and break 5 A at 250 Vac (80% PF), 5 A at 28
Vdc (resistive), and 0.5 A at 120 Vdc (resistive).

Tolerances

Advance Angle

The command for breaker closure occurs within

±3.0° of phase

coincidence of bus and generator. (Closure will not occur if the
calculated advance angle exceeds 40

°.)

Lockout

Occurs when breaker reopens within 15

±10% seconds after the

initiation of breaker closure.

Slip Frequency (

F

S

)

±0.001 Hz

Generator Undervoltage

±1.0 V

Inhibit

Control Ranges

The following parameters are settable over the indicated ranges.

MAX SLIP

Adjustable from 0.01 to 0.500 in steps of 0.001.

BRKR TIME

The characteristic breaker time settings are adjustable from 0.02 to
0.8 seconds.

Generator Undervoltage

Adjustable from 40 to 110 Vac.

Inhibit

NOTE

When a sync output closure is initiated, the sync output contact will be held
closed for the duration of the Breaker Operating Time setting (or 250 ms
minimum).

1-6

BE1-25A General Information

9146600990 Rev S