SECTION 4

• INSTALLATION

INTRODUCTION

BE1-25A relays are shipped in sturdy cartons to prevent damage during transit. Upon receipt of a relay,
check the model and style number against the requisition and packing list to see that they agree. Inspect
the relay for shipping damage. If there is evidence of damage, file a claim with the carrier, and notify your
sales representative or Basler Electric.

If the relay will not be installed immediately, store it in its original shipping carton in a moisture- and dust-
free environment. Before placing the relay in service, it is recommended that the test procedures of
Section 5, Testing be performed.

RELAY OPERATING GUIDELINES AND PRECAUTIONS

Before installing or operating the relay, note the following guidelines and precautions.

When the unit is installed, the controls should be protected by the plastic cover supplied. This limits
access to the control settings.

MOUNTING

BE1-25A Synchronizers are designed to be rack-mounted. The overall dimensions are shown in Figure
4-1.
Alternatively, the unit may be panel-mounted, using the cutout dimensions of Figure 4-2 as a guide.
The unit may be mounted at any convenient angle.

NOTE

Be sure that the BE1-25A is hard-wired to earth ground with no smaller than 12
AWG copper wire attached to the ground terminal on the rear of the case. When
the BE1-25A is configured in a system with other devices, it is recommended to
use a separate lead to the ground bus from each device.

9146600990 Rev S

BE1-25A Installation

4-1