B3 and b5 calibration, B3 and b5 calibration -9 – Basler Electric BE1-25A User Manual

Page 79

Advertising
background image

Figure 6-7. Module B3 Block Diagram

Figure 6-8. Module B5 Block Diagram

B3 and B5 Calibration

1. Connect the oscilloscope or frequency counter to the synchronizer module front panel pin jacks.

Set the trigger to detect negative going (+12 to O V) pulses.

2. Set the front panel BREAKER SELECT switch to A.

3. Adjust the A control on the breaker time equalization option module for the desired time. Note that

the internal relay pickup time (nominal 15 ms) is not included in the above measurement.

4. Repeat the above steps for breaker times B, C, D, and E as desired.

9146600990 Rev S

BE1-25A Relay Differences

6-9

Advertising