Outputs, Options, Outputs -4 – Basler Electric BE1-25A User Manual

Page 38: Options -4

Advertising
background image

then inhibited until such time as all vital voltages return to normal. (Because all settings and vital,
programming instructions are held in non-volatile memory (EEPROM), and are not erased if power is
lost.)

Microprocessor operation is monitored by the watchdog circuitry. If some transient condition has disrupted
the normal pattern of operation, the watchdog operates the alarm output, resets the microprocessor, and
initializes the program. The reset restarts the microprocessor. After the third such reset operation
(perhaps indicative of some hardware failure), the microprocessor is stopped and shuts down the entire
unit. This condition remains until operating power is disconnected, then reapplied. (An inoperative
microprocessor usually appears as a display that is frozen and probably inappropriate or meaningless.)

OUTPUTS

Again referencing Figure 3-2, the Output Drivers provide the interface required between the logic circuits
and the final outputs, which are the LED indicators and the output relays. The Breaker Close relay
provides a normally open contact. The other output relays are of the plug-in type, and are only
incorporated into the unit upon the addition of the relevant option(s). Note that these supplementary
relays provide both normally open and normally closed contacts for each function represented. (For the
terminal numbers of these contacts see Section 4, Installation.)

OPTIONS

The various options available for the BE1-25A Auto-Synchronizer Relay are described on the following
pages. Note that they are grouped into four categories: Voltage Acceptance, Voltage Matching,
Frequency Matching,
and Dead Bus. Only one option from each category can be used at one time.

The basic Synchronizer may be upgraded to Automatic Synchronizer status by incorporating one of the
voltage matching options and/or one of the frequency matching options. This may be accomplished at any
time

− i.e., at original purchase or at any time thereafter.

Legend for Figure 3-3.

ADVANCE ANGLE - Number of degrees that the close breaker signal must precede

actual closure of the breaker so that the closure occurs at (or very
close to) zero degrees of phase difference

BF - Bus frequency

CLOSE BREAKER - Represent the closure of the BE1-25A output contact to provide

closing current to the breaker

DEAD BUS - A condition where the bus voltage is less than the setting of module

D1, VOLTS control

GF - Generator frequency

GV - Generator voltage

MAX SLIP - Maximum slip frequency setting

F

S

- Slip frequency

UV - Undervoltage Setting

3-4

BE1-25A Functional Description