SPECIFICATIONS OF OPTIONS

To eliminate repetition, only the specifications that uniquely apply to a particular option are given below.
Specifications that are applicable throughout the unit (including the options) are stated above.

Voltage Acceptance Option A1

VOLTAGE DIFFERENCE CONTROL

Minimum threshold adjustable from 0.5 to 5% of
generator voltage. (Generator voltage minus bus
voltage)

Weight

6.6 oz (186.0 g)

Voltage Acceptance Option A2

BUS VOLTAGE UPPER LIMIT CONTROL

Maximum threshold adjustable from 100 to 150 Vac.

BUS VOLTAGE LOWER LIMIT CONTROL

Minimum threshold adjustable from 80 to 120 Vac.

VOLTAGE DIFFERENCE CONTROL

Minimum threshold adjustable from 1 to 10 Vac of
generator voltage. (Generator voltage minus bus
voltage)

Weight

8 oz (226.8 kg)

Frequency Matching Option F5

CORRECTION PULSE WIDTH CONTROL

Adjustable from 0 to 99.9 seconds.

CORRECTION PULSE INTERVAL CONTROL

Adjustable from 0 to 99.9 seconds.

Weight

6.6 oz (186.0 g)

Voltage Matching Option V1

Weight

5 oz (140.6)

Voltage Matching Option V2

CORRECTION PULSE WIDTH CONTROL

Adjustable from 0.1 to 5.0 seconds.

CORRECTION PULSE INTERVAL CONTROL

Adjustable from 0.2 to 10.0 seconds.

Weight

7.0 oz (200.0 g)

Voltage Matching Option V3

CORRECTION PULSE WIDTH CONTROL

Adjustable from 0.1 to 5.0 seconds.

CORRECTION PULSE INTERVAL CONTROL

Adjustable from 0.2 to 10.0 seconds.

Weight

8.5 oz (240.4 g)

Dead Bus Option D1

VOLTS CONTROL

Adjustable from 10.0 to 40.0 Vac.

Weight

6.6 oz (186.0 g)

1-8

BE1-25A General Information

9146600990 Rev S