Calibration instructions, Calibration instructions -6 – Basler Electric BE1-25A User Manual

Page 76

Advertising
background image

The differentiator produces a dc voltage proportional to the rate of change of the input triangular
waveform, and outputs this voltage to the breaker time compensation circuit, the in sync/in phase circuit,
the comparator, and the precision full wave rectifier. The dc output of the precision full wave rectifier is
further smoothed by the sample and hold circuit. The sample and hold circuit output is input to the in
sync/in phase circuit and to the slip frequency comparator.

If the input signal to the slip frequency comparator exceeds the front panel SLIP FREQUENCY
adjustment setting (i.e. the reference), an inhibit signal is delivered to the output gate and the front panel
FS HIGH indicator illuminates. When the input slip frequency signal is less than the front panel SLIP
FREQUENCY setting, an enable signal is sent by the inhibit gate to the in-sync output gate to permit
breaker closure when the other conditions are met.

If the phase angle is greater than 40°, the 40° inhibit sync circuit outputs an inhibit signal to the inhibit
gate.

The lockout circuit will generate an inhibit signal such that if the generator breaker opens within 15
seconds after closing, the synchronizer will not attempt to reclose the relay. The lockout circuit outputs
are sent to the sync circuits, the timer, and to any options. In addition, the front panel LOCKOUT indicator
will illuminate. This function may be reset by use of the LOCKOUT RESET switch, or by an external
contact closure. A circuit-board-mounted switch (S2 of the circuit board) can be used to disable or enable
this function.

The inhibit gate receives the generator frequency greater than bus frequency (GF>BF) signal, the
differentiator output, and any option outputs. These are compared, and when the generator frequency,
bus frequency, and phase angle are within limits, an enable signal is output to the in sync output gate.
This is acknowledged by the illumination of the SYNC indicator.

The breaker time timer will start timing as soon as the close signal is sent to the generator breaker. The
period of this timer is adjusted by the BREAKER CLOSING TIME control. When the timer times out (at
0°), a reset signal is output to the in sync output gate to remove the close breaker signal, and a remove
correction signal is output to the V and F options.

When the in sync/in phase circuit inputs (from the differentiator circuit and the sample and hold circuit)
indicate less than 0.008 Hz frequency difference and less than a 3°

±1° phase angle difference, the timer

will time out provided there are no inhibits present. After two seconds, a 100 ms pulse is output to the
relay driver to close the controlled breaker.

The sensed bus voltage is rectified and output to the comparator shown at bottom left of Figure 6-4,
where it is compared to a reference level that is controlled at the front panel. If the bus is below the front
panel setting, a dead bus signal is output.

Sensed generator voltage is rectified and output to two comparators shown at bottom right of Figure 6-4.
One comparator compares the generator voltage to the front panel UNDERVOLTAGE INHIBIT ADJUST
reference. When the generator voltage is below the reference, it produces an undervoltage signal and
illuminates the UNDERVOLTAGE INHIBIT indicator. The other comparator compares the generator
voltage to a fixed reference. If the generator voltage is below the fixed reference, a dead generator signal
is output.

An out-of-range signal (right center of Figure 6-4) is generated if the differentiator output indicates that the
bus and generator frequency difference is greater than a preset value, thereby inhibiting synchronization.

Calibration Instructions

Equipment Required

• Two frequency-adjustable voltage sources for the generator and bus sensing inputs. Requires a

low-distortion output with a voltage range of 70-150 Vac, and a frequency that is adjustable in
0.005 Hz increments. (The use of less accurate sources will result in less accurate settings.)

• Input power source capable of either 90-132 Vac at 50/60 Hz, or 70-150 Vdc
• Oscilloscope or counter for measuring pulse width
• AC Voltmeter
• Synchroscope
• Switches or jumpers for enabling the 52b, GF>BF, GV>BV, and dead bus functions

6-6

BE1-25A Relay Differences

9146600990 Rev S

Advertising