5.14 Back-to-Back MII Connection

5.14.1 ESC to ESC Connection

Two EtherCAT slave controllers can be connected back-to-back using MII as shown in the figure
below. The timing of RX_DV and RXD with respect to RX_CLK has to be checked at both ESCs to be
compliant with the IEEE 802.3 requirements of min. 10 ns setup time and min. 10 ns hold time. The
timing can be adjusted by configuring the TX Shift settings of each ESC.

Enhanced Link Detection cannot be enabled for the back-to-back ports on both ESCs.

Other clocking options besides using quartz oscillators are also possible. If CLK25_OUT is not
available, REF_CLK can be used instead.

ESC

REF_CLK

LINK_MII*

RX_CLK

RX_DV

RXD[3:0]

TX_CLK

TX_EN

TXD[3:0]

RX_ER

MDC

MDIO

ESC

REF_CLK

RESET*

RX_CLK

RX_DV

RXD[3:0]

TX_CLK

TX_EN

TXD[3:0]

RX_ER

MDC

MDIO

25 MHz

4

K

7

* check polarity: active Reset = no link

V

CC I/O

4

K

7

V

CC I/O

Configure TX Shift and
check RX timing
(setup/hold>10 ns)

Configure TX Shift and
check RX timing
(setup/hold>10 ns)

CLK25_OUT

25 MHz

CLK25_OUT

LINK_MII*

RESET*

Single clock source is
possible, too.

Figure 14: Back-to-Back MII Connection (two ESCs)