I.9 parameter table – Yaskawa iQpump Micro Quick Start User Manual

Page 100

Advertising
background image

No.

Name

Description

P9-09

Add Frequency Level

When P9-08 is set to 0, this parameter sets

the level above which the output frequency

needs to rise for the time set in P9-11 before

the lead drive will send a request for a new

lead drive via the iQPump MEMOBUS

network.

When P9-08 is set to 2 and the delta

feedback (setpoint minus feedback) has

exceeded the level set in P9-10 for the time

set in P9-11, this parameter sets the level

above which the output frequency needs to

rise before the lead drive will send a request

for a new lead drive via the iQPump

MEMOBUS network.

P9-10

Add Delta Level

When P9-08 is set to 1, this parameter sets

the level above which the delta feedback

(setpoint minus feedback) must rise for the

time set in P9-11 before the lead drive will

send a request for a new lead drive via the

iQPump MEMOBUS network.

When P9-08 is set to 2 and the output

frequency has exceeded the level set in

P9-09 for the time set in P9-11, this

parameter sets the level above which the

delta feedback (setpoint minus feedback)

needs to rise before the lead drive will send

a request for a new lead drive via the

iQPump MEMOBUS network.

P9-11

Add Delay Time

Sets the delay time before a new lead drive

is added to the system.

P9-12

Remove Pump Mode

0: Output frequency

1: Feedback

2: Feedback + Fout

P9-13

Remove Frequency

Level

When P9-12 is set to 0, this parameter sets

the level below which the output frequency

must fall for the time set in P9-15 before the

lead drive will send a request to be removed

from the system via the iQPump

MEMOBUS network.

When P9-12 is set to 2 and the delta

feedback (feedback minus setpoint) has

exceeded the level set in P9-14 for the time

set in P9-15, this parameter sets the level

below which the output frequency must fall

before the lead drive will request to be

removed from the system via the iQPump

MEMOBUS network.

P9-14

Remove Delta Level

When P9-12 is set to 1, this parameter sets

the level above which the delta feedback

(feedback minus setpoint) must rise for the

time set in P9-15 before the lead drive will

request to be removed from the system via

the iQPump MEMOBUS network.

When P9-12 is set to 2 and the output

frequency has exceeded the level set in

P9-13 for the time set in P9-15, this

parameter sets the level above which the

delta feedback (feedback minus setpoint)

frequency must rise before the lead drive

will request to be removed from the system

via the iQPump MEMOBUS network.

P9-15

Remove Delay Time

Sets the delay time before the lead drive is

removed from the system.

P9-16

Stabilization Time

Sets the time used to stabilize the system

when a pump is staged or de-staged.

Lead/lag control and pump protection are

suspended during this time.

P9-17

Setpoint Modifier

Sets the value by which the system setpoint

is incremented depending on the number of

pumps that are running.

Pump 1: Setpoint

Pump 2: Setpoint + ((X-1) (P9-17))

No.

Name

Description

P9-18

High Feedback Quick

De-Stage

Sets the feedback level that will trigger a

quick de-stage. Set as a percentage of the

P1-11 value.

The quick de-stage ignores parameters

P9-12 to P9-15 and uses an internal 2

second delay.

Setting this parameter to 0.0 disables the

feature.

P9-19

Alternation Unit

Sets the units used in P9-03.

0: Hours (H)

1: Minutes (min)

P9-20

Allow Network Run

0: Always

1: First/alternation

2: First only

3: Alternation only

P9-21

Run Priority

Sets the lead drive selection priority

overriding the P9-01 selection. Lower value

= Higher priority.

If multiple drives have the lowest P9-21

value, then P9-01 determines which drive

becomes the lead.

P9-22

System Fault Retry

Sets the number of times that the iQPump

MEMOBUS network will allow automatic

restarts of system faults.

The drive uses L5-04, Fault Reset Interval

Time, to determine when to attempt a

system fault restart.

Set this parameter to the same value for all

drives on the network.

P9-23

Maximum Number of

Running Pumps

Sets the maximum number of pumps that

can run on the system.

P9-24

Lead Swap at Sleep

Sets the length of time for which the lead

drive will be in Sleep Mode before this drive

will request a swap when there is another

drive available with a lower P9-21 setting.

Setting this parameter to 0 will disable the

function.

P9-25

Highest Node Address

Sets the highest possible node address in the

MEMOBUS network.

For optimal network performance, set the

serial communication address H5-01

beginning with 01h consecutively up to the

last drive and then set this parameter to that

H5-01 address.

P9-26

Master Time-out

Sets the minimum amount of time that the

slave drives will wait for a message from

the master before performing the action set

in P9-27.

P9-27

Network Recovery

0: Automatic. The drive will attempt to

assume master functionality.

1: Slave/Resume. The drive will continue

running when the master is lost and will

wait for a master to come online.

2: Slave/Stop. The drive will stop running

when the master is lost and will wait for a

master to come online.

3: Fault MSL. Fault the drive with an MSL

(Master Lost).

P9-28

NETSCAN Alarm

Time

Sets the amount of time that the slave drives

will wait for a message from the master

before displaying a NETSCAN alarm.

P9-29

Net Start Delay

Sets the amount of time that the network

will wait before selecting and starting the

lead drive after the first drive on the network

has been put on AUTO Mode.

P9-30

Lag Drive Speed

Follower Gain

Sets the gain to be applied to the speed of

the current lead drive when P9-05 is set to

3. The bias to be applied is set in P9-31.

P9-31

Lag Drive Speed

Follower Bias

Sets the bias to be applied to the speed of

the current lead drive when P9-05 is set to

3. The gain to be applied is set in P9-30.

i.9 Parameter Table

100