Mechanical installation, Installation environment, Installation orientation and spacing – Yaskawa iQpump Micro Quick Start User Manual

Page 39: I.3 mechanical installation

Advertising
background image

i.3

Mechanical Installation

This section outlines specifications, procedures, and environment for proper mechanical installation of the drive.

u

Installation Environment

To help prolong the optimum performance life of the drive, install the drive in the proper environment.

Table i.1

describes

the appropriate environment for the drive.

Table i.1 Installation Environment

Environment

Conditions

Installation Area

Indoors

Ambient Temperature

IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)

IP66/NEMA Type 4X enclosure: -10 °C to +40 °C (14 °F to 104 °F)

Drive reliability improves in environments without wide temperature fluctuations.

When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside

the enclosure does not exceed the specified levels.

Do not allow ice to develop on the drive.

Humidity

95% RH or less and free of condensation

Storage Temperature

-20 °C to +60 °C (-4 °F to +104 °F)

Surrounding Area

Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
For IP66/NEMA Type 4X enclosure drives, install the drive in an environment suitable for IP66/NEMA Type 4X

enclosures:
• NEMA Type 4X – Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel

against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet,

snow, windblown dust, splashing water, hose-directed water, and corrosion; and that will be undamaged by the external

formation of ice on the enclosure.

• IP66 – Dust-tight enclosures to do not allow any dust to penetrate. The enclosure guards the drive against powerful

jetting water sprayed from any direction and is protected against access to hazardous parts with a wire.

Altitude

Up to 1000 meters without derating; up to 3000 meters with output current, ambient temperature, and voltage derating.

Vibration

10 to 20 Hz at 9.8 m/s

2

20 to 55 Hz at 5.9 m/s

2

Orientation

Install the drive vertically to maintain maximum cooling effects.

NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project

construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation.

Remove the temporary cover before startup, as the cover will reduce ventilation and cause the drive to overheat.

NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive. Failure to comply could result in erroneous

operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.

u

Installation Orientation and Spacing

NOTICE: Install the drive upright as illustrated in

Figure i.5

. Failure to comply may damage the drive due to improper cooling.

Figure i.5 Correct Installation Orientation

i.3 Mechanical Installation

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide

39

Advertising