Output frequency when

Stop command was entered

100%

(Maximum output

frequency)

10%

DC Injection braking time

b2-04×10

b2-04

Figure i.36 DC Injection Braking Time Depending on Output Frequency

Note:

If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no

longer occurs.

Setting 3: Coast to Stop with Timer (Used for Back Spin Control on Vertical Turbine Pumps)

When the Run command is removed, the drive coasts to a stop. If parameter b1-11 = 0, the coast-timer (Run Delay at Stop)

becomes a value determined by a combination of output frequency and C1-02. However, if b1-11 > 0, the Run Delay at Stop

timer is set to b1-11. If the Run command is reissued during the Run Delay at Stop timer time, the drive WILL restart when

the timer expires without the need to re-cycle the Run command. The Run Delay at Stop timer will operate for both AUTO

Mode and HAND Mode. The Run Delay at Stop timer will still operate when the drive goes to sleep and then wakes up. During

the Run Delay at Stop timer execution, the HOA keypad will display a Start Delay message.

Drive output shut off

Run wait time t

Run command

Output

frequency

ON

ON

ON

OFF

OFF

Figure i.37 Coast to Stop with Timer

The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.

Min output

frequency

100%

(Max output

frequency)

Output frequency

when Stop command

was entered

Run wait time t

Active deceleration time

Momentary Power Loss
Minimum Baseblock
Time (L2-03)

Figure i.38 Run Wait Time Depending on Output Frequency

n

b3-01: Speed Search Selection at Start

Determines if Speed Search is automatically performed when a Run command is issued.

No.

Parameter Name

Setting Range

Default

b3-01

Speed Search Selection at Start

0, 1

0

Setting 0: Disabled

This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed

Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.

i.6 Start-Up Programming and Operation

72