Digital Operator

Display

Alarm Name

bUS

Option Communication Error
• The connection was lost after establishing initial communication.
• Only detected when the run command frequency reference is assigned to an option card.

CALL

Serial Communication Transmission Error
Communication has not yet been established.

CE

MEMOBUS/Modbus Communication Error
Control data was not received for the CE detection time set to H5-09.

CrST

Cannot Reset

CyC

MECHATROLINK Comm. Cycle Setting Error
Comm. Cycle Setting Error was detected.

dnE

Drive Disabled

E5

SI-T3 Watchdog Timer Error
The watchdog timed out.

EF

Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for longer than 0.5 s.

EF0

Option Card External Fault
An external fault condition is present.

EF1

Pump Fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

Pump Fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

Pump Fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

Pump Fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

Pump Fault (input terminal S5)
External fault at multi-function input terminal S5.

EF6

Pump Fault (input terminal S6)
External fault at multi-function input terminal S6.

EF7

Pump Fault (input terminal S7)
External fault at multi-function input terminal S7.

EoF

Emergency Override Forward Run

Eor

Emergency Override Reverse Run

FAn

Internal Cooling Fan Error

Hbb

Safe Disable Signal Input
Both Safe Disable Input channels are open.

HbbF

Safe Disable Signal Input
One Safe Disable channel is open while the other channel is closed.

Feedback Loss Go To

Freq. b5-13

(FLGT)

PI Feedback Loss

The drive will run at the speed set in b5-13, Feedback Loss Goto Frequency.

Feedback Loss Wire

Break

(FDB-L)

PI Feedback Loss

The analog input programmed for PID feedback has gone above 21 mA or fallen below 3 mA.

Freq. Ref Pump Min

(P1-06)

(PFREF)

Minimum Pump Frequency Reference

Drive frequency reference is set lower than P1-06, Minimum Pump Frequency.

Freq. Ref Thrust (P4-12)

(PTHRT)

Thrust Frequency Reference
The fixed frequency reference is set to a value lower than the P4-12, Thrust Frequency, setting.

HCA

Current Alarm
Drive current exceeded overcurrent warning level (150% of the rated current).

i.7 Troubleshooting

82