Setting 6008: Pressure Control

Application Preset for Pressure Control applications.

Setting 6009: Pump Down Level

Application Preset for Pump Down Level applications.

Setting 7770: General Purpose

General Purpose Application Preset.

Setting 7771: Submersible Motor General Purpose Operation

General Purpose Application Preset.

n

b1-01: Frequency Reference Selection 1

Selects the frequency reference source 1 for the AUTO mode.

Note:

If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator LED

on the digital operator will light and the STOP indicator will flash.

No.

Parameter Name

Setting Range

Default

b1-01

Frequency Reference Selection 1

0 to 4

0

In order to run the drive and motor, the drive must receive a Run command and an Auto Setpoint command. Parameter b1-01

specifies the origin of the Auto setpoint when in AUTO Mode. Switch to AUTO mode by pressing the AUTO button on the

HOA keypad while the drive is stopped.

Note:

If a Run command is input to the drive without a corresponding Auto setpoint, the Run indicator on the HOA keypad will turn on and the

STOP indicator on the keypad will blink.

If the drive should follow the “HAND Reference” set by the HOA keypad, use HAND Mode by pressing the HAND key and

set P5-01 to “1: Hand Reference (P5-02).” The HAND reference can then be entered into the U1-01 monitor parameter in the

“-DRIVE-” Menu.
The drive offers the ability to provide four types of “Auto Setpoint” reference sources. These Auto Setpoint reference sources

are determined by the setting of b1-01 and the drive set to AUTO Mode by pressing the AUTO key on the keypad.
Prior to programming, it is recommended to select the system units (P1-02) and the feedback device, Scaling (P1- 03) first.

P1-03 will automatically scale the drive setpoint.
Example: P1-02 = 1: PSI
P1-03 = 200, feedback range = 200 PSI.
If the drive should follow an “Auto Set-Point” set by the HOA keypad: Set b1-01 to “0: Operator” (factory default). The Auto

setpoint can then be entered into the U5-99 monitor parameter in the “-DRIVE-” menu.

Setting 0: Operator (HOA keypad)

Using this setting, the frequency reference can be input by:
• switching between the multi-speed references in the d1-oo parameters.
• entering the frequency reference on the operator keypad.
This selection will also switch PID setpoint to Q1-01.

Setting 1: Terminals (Analog Input Terminals)

Using this setting, an analog frequency reference can be entered from:
• Terminal A1 using a 0 to 10 Vdc signal.
• Terminal A2 using either a 0 to 10 Vdc or a 0/4 to 20 mA signal.

Note:

Terminal A2 supports voltage and current input. The input signal type must be set up by setting DIP switch S1 and adjusting parameter

H3-09.

Entering only the main frequency reference:
Using Control Circuit Terminal A1 (0 to 10 Vdc voltage input):
Use a circuit such as the one shown in

Figure i.30

or an external 0 to 10 Vdc voltage source like a PLC analog output and set

the input level selection for A1 in parameter H3-02 as desired.

i.6 Start-Up Programming and Operation

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide

67