Wire the control terminals using, Figure i.17, Figure i – Yaskawa iQpump Micro Quick Start User Manual

Page 53: I.5 main circuit wiring

Advertising
background image

NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may damage the terminal block.

NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring practices could result in drive or

equipment malfunction due to electrical interference.

Connect control wires as shown in the following figure:

Preparing wire
terminal ends

E

A

B

D

C

A – Control terminal block
B – Avoid fraying wire strands when

stripping insulation from wire. Strip
length 5.5 mm.

C – Single wire or stranded wire

D – Loosen screw to insert wire.
E – Blade depth of 0.4 mm or less

Blade width of 2.5 mm or less

Figure i.17 Terminal Board Wiring Guide

A

F

C

D

E

B

A – Drive side
B – Connect shield to ground terminal

of drive.

C – Insulation

D – Control device side
E – Shield sheath (Insulate with tape)
F – Shield

Figure i.18 Preparing the Ends of Shielded Cables

When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires and ground

the shield of twisted-pair wires to the ground terminal of the drive.

NOTICE: The analog signal lines between the drive and the operator station or peripheral equipment should not exceed 50 meters when

using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.

RP

+V

A1

A2

AC

A

B

C
D

E
F

G

2 k

A – Drive
B – Ground terminal (shield

connection)

C – (RP) Pulse train (maximum 32 kHz)
D – (+V) Frequency setting power

source +10.5 Vdc maximum 20 mA

E – (A1) Main speed frequency

reference 0 to +10 Vdc (20 kΩ)

F – (A2) Multi-function analog input

0 to +10 Vdc (20 kΩ) or
4 to 20 mA (250 Ω)/
0 to 20 mA (250 Ω)

G – Frequency setting potentiometer

Figure i.19 Wiring the Frequency Reference to the Control Circuit Terminals (External Reference)

i.5 Main Circuit Wiring

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide

53