I.9 parameter table – Yaskawa iQpump Micro Quick Start User Manual

Page 101

Advertising
background image

No.

Name

Description

P9-32

Lag Follower

Deceleration Time

Sets the deceleration time when the P9-33

timer is running and the drive is running as

Lag Drive Speed Follower

(P9-05 is set to 3).

P9-33

Lag Follower

Deceleration Time

Active Time

Sets the time during which the deceleration

time set in P9-32 is effective. The drive will

use the standard deceleration rate when it

expires.

Setting this parameter to 0.0 disables the

function.

P9-34

Low Feedback Quick

De-Stage

Sets the low feedback level that will trigger

a quick de-stage.

The quick de-stage ignores parameters

P9-12 and P9-15 and only uses an internal

2 second delay.

Setting this parameter to 0.0 disables the

function.

P9-99

Network Compatibility

Selection

0: A-Ver: 30034

1: B-Ver: 30035/36

2: iQ SmartNetwork

Q1-01

PID Controller

Setpoint 1

Sets the PID Setpoint when b1-01 is set to

0.

Q1-02

PID Controller

Setpoint 2

Sets the PID Setpoint when the “Multi

Setpoint 1” or "Alternate Multi Setpoint 1"

multi-function digital input is closed.

Q1-03

PID Controller

Setpoint 3

Sets the PID Setpoint when the “Multi

Setpoint 2” or "Alternate Multi Setpoint 2"

digital input is closed.

Q1-04

PID Controller

Setpoint 4

Sets the PID Setpoint when the “Multi

Setpoint 1” and “Multi Setpoint 2” or

“Alternate Multi Setpoint 3” multi-function

digital inputs are closed.

No.

Name

Description

Q1-09

PID Setpoint Set via

Motor Operated Pot

Selects whether parameters Q1-01 to Q1-04

are changed via MOP from the home

screen.

0: Disabled

1: Enabled

Q3-01

Output Current Limit

Select

0: Disabled

1: Enabled

Q3-02

Current Limit

Sets the current limit. Value is internally

limited to 300% of the drive rated current.

Q3-10

Ripple Regulator

Selection

0: Disabled

1: Enabled

2: Enabled w/ Line Reactor

Q3-11

Ripple Regulator

Setpoint

Set as a percentage of the maximum amount

of ripple allowed before triggering an input

phase loss fault.

S6-01

Emergency Override

Speed

Sets the speed command used in emergency

override mode when S6-02 = 0.

S6-02

Emergency Override

Reference Selection

0: Use S6-01 Reference

1: Use Frequency Reference

T1-01

Auto-Tuning Mode

Selection

2: Stationary Auto-Tuning for Line-to-

Line Resistance

T1-02

Motor Rated Power

Sets the motor rated power as specified on

the motor nameplate.

T1-04

Motor Rated Current

Sets the motor rated current as specified on

the motor nameplate.

i.9 Parameter Table

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide

101