I.9 parameter table – Yaskawa iQpump Micro Quick Start User Manual

Page 93

Advertising
background image

No.

Name

Description

E2-04

Number of Motor Poles Sets the number of motor poles.

Automatically set during Auto-Tuning.

E2-05

Motor Line-to-Line

Resistance

Sets the phase-to-phase motor resistance.

Automatically set during Auto-Tuning.

E2-06

Motor Leakage

Inductance

Sets the voltage drop due to motor leakage

inductance as a percentage of motor rated

voltage. Automatically set during

Auto-Tuning.

E2-10

Motor Iron Loss for

Torque Compensation Sets the motor iron loss.

E2-11

Motor Rated Power

Sets the motor rated power in kilowatts

(1 HP = 0.746 kW). Automatically set

during Auto-Tuning.

H1-01 to

H1-07

Multi-Function Digital

Input Terminal S1 to

S7 Function Selection

Selects the function of terminals S1 to S7.

H1-21

External Fault 1 Delay

Time

Sets the amount of time delay applied to the

EF1 fault. (20 ≤ H1-01 ≤ 2F)

H1-22

External Fault 2 Delay

Time

Sets the amount of time delay applied to the

EF2 fault. (20 ≤ H1-02 ≤ 2F)

H1-23

External Fault 3 Delay

Time

Sets the amount of time delay applied to the

EF3 fault. (20 ≤ H1-03 ≤ 2F)

H1-24

External Fault 4 Delay

Time

Sets the amount of time delay applied to the

EF4 fault. (20 ≤ H1-04 ≤ 2F)

H1-25

External Fault 5 Delay

Time

Sets the amount of time delay applied to the

EF5 fault. (20 ≤ H1-05 ≤ 2F)

H1-26

External Fault 6 Delay

Time

Sets the amount of time delay applied to the

EF6 fault. (20 ≤ H1-06 ≤ 2F)

H1-27

External Fault 7 Delay

Time

Sets the amount of time delay applied to the

EF7 fault. (20 ≤ H1-07 ≤ 2F)

H2-01

Terminal MA, MB, and

MC function selection

(relay)

Sets the function for terminals

MA/MB/MC.

H2-02

Terminal P1 function

selection (open-

collector)

Sets the function for the terminal P1.

H2-03

Terminal P2 function

selection (open-

collector)

Sets the function for terminal P2.

H2-06

Power Consumption

Output Unit Selection

0: 0.1 kWh units

1: 1 kWh units

2: 10 kWh units

3: 100 kWh units

4: 1000 kWh units

H3-01

Terminal A1 Signal

Level Selection

0: 0 to 10 V

1: -10 to 10 V

H3-02

Terminal A1 Function

Selection

Sets the function of terminal A1.

H3-03

Terminal A1 Gain

Setting

Sets the level of the input value selected in

H3-02 when 10 V is input at terminal A1.

H3-04

Terminal A1 Bias

Setting

Sets the level of the input value selected in

H3-02 when 0 V is input at terminal A1.

H3-09

Terminal A2 Signal

Level Selection

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

3: 0 to 20 mA

Note: Use DIP Switch S1-2 to set input

terminal A2 for a current or voltage input

signal.

H3-10

Terminal A2 Function

Selection

Sets the function of terminal A2.

H3-11

Terminal A2 Gain

Setting

Sets the level of the input value selected in

H3-10 when 10 V (20 mA) is input at

terminal A2.

No.

Name

Description

H3-12

Terminal A2 Bias

Setting

Sets the level of the input value selected in

H3-10 when 0 V (0 or 4 mA) is input at

terminal A2.

H3-13

Analog Input Filter

Time Constant

Sets a primary delay filter time constant for

terminals A1 and A2. Used for noise

filtering.

H3-14

Analog Input Terminal

Enable Selection

1: Terminal A1 only

2: Terminal A2 only

7: All terminals enabled

H3-16

Terminal A1 Offset

Adds an offset when the analog signal to

terminal A1 is at 0 V.

H3-17

Terminal A2 Offset

Adds an offset when the analog signal to

terminal A2 is at 0 V.

H4-01

Multi-Function Analog

Output Terminal AM

Monitor Selection

Selects the data to be output through multi-

function analog output terminal AM.

Set the desired monitor parameter to the

digits available in Uo-oo.

For example, enter “103” for U1-03.

H4-02

Multi-Function Analog

Output Terminal AM

Gain

Sets the signal level at terminal AM that is

equal to 100% of the selected monitor

value.

H4-03

Multi-Function Analog

Output Terminal AM

Bias

Sets the signal level at terminal AM that is

equal to 0% of the selected monitor value.

H5-01

Drive Node Address

Selects drive station node number (address)

for MEMOBUS/Modbus terminals R+, R-,

S+, S-. Cycle power for the setting to take

effect.

H5-02

Communication Speed

Selection

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Cycle power for the setting to take effect.

H5-03

Communication Parity

Selection

0: No parity

1: Even parity

2: Odd parity

Cycle power for the setting to take effect.

H5-04

Stopping Method After

Communication Error

(CE)

0: Ramp to stop

1: Coast to stop

2: Fast Stop

3: Alarm only

H5-05

Communication Fault

Detection Selection

0: Disabled

1: Enabled. If communication is lost for

more than two seconds, a CE fault will

occur.

H5-06

Drive Transmit Wait

Time

Set the wait time between receiving and

sending data.

H5-07

RTS Control Selection

0: Disabled. RTS is always on.

1: Enabled. RTS turns on only when

sending.

H5-09

CE Detection Time

Sets the time required to detect a

communications error.

H5-10

Unit Selection for

MEMOBUS/Modbus

Register 0025H

0: 0.1 V units

1: 1 V units

H5-11

Communications

ENTER Function

Selection

0: Drive requires an Enter command

before accepting any changes to

parameter settings.

1: Parameter changes are activated

immediately without the Enter command.

H5-12

Run Command

Method Selection

0: FWD/Stop, REV/Stop

1: Run/Stop, FWD/REV

i.9 Parameter Table

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide

93