Menu structure for digital led operator, Powering up the drive, 1> reverse can only be selected when local is set – Yaskawa iQpump Micro Quick Start User Manual

Page 59: I.6 start-up programming and operation, Programming mode drive mode

Advertising
background image

No.

Display

Name

Function

16

Communication Port

Port used for USB Copy Unit, LCD Operator Keypad, and for connecting to a PC.

NOTICE: Use only specified cable when making connections to the drive. Failure

to comply may damage the drive.

NOTICE: Do not open the port cover wider than 90 degrees. Failure to comply

may break the port cover and leave the unprotected port susceptible to damage.

u

Menu Structure for Digital LED Operator

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

X

:

:

:

:

Turn the power on

Forward Selection

Reverse Selection

Output Frequency

Output Current

Output Voltage

Monitor Display

Verify Menu

Set Up Mode

Parameter Setting Mode

Auto-Tuning

Description of Key Operations

Note: “XX” characters are shown in this manual.

The drive will display the actual setting values.

PROGRAMMING MODE

DRIVE MODE

<1>

Application Preset

Figure i.24 Digital LED Operator Screen Structure

<1> Reverse can only be selected when LOCAL is set.

n

Powering Up the Drive

Review the following checklist before turning the power on.

Item to Check

Description

Power supply voltage

Ensure the power supply voltage is correct:

200 V class: single-phase 200 to 240 Vac 50/60 Hz

200 V class: 3-phase 200 to 240 Vac 50/60 Hz

400 V class: 3-phase 380 to 480 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).

(for single-phase 200 V class models, wire only R/L1 and S/L2)
Check for proper grounding of drive and motor.

Drive output terminals

and motor terminals

Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, and W.

Control circuit terminals

Check control circuit terminal connections.

Drive control terminal status

Open all control circuit terminals (off).

Status of the load

and connected machinery

Uncouple the motor from the load.

i.6 Start-Up Programming and Operation

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide

59