I.9 parameter table – Yaskawa iQpump Micro Quick Start User Manual

Page 94

Advertising
background image

No.

Name

Description

H6-01

Pulse Train Input

Terminal RP Function

Selection

0: Frequency reference

1: PID feedback value

2: PID setpoint value

H6-02

Pulse Train Input

Scaling

Sets the terminal RP input signal frequency

that is equal to 100% of the value selected

in H6-01.

H6-03

Pulse Train Input Gain

Sets the level of the value selected in H6-01

when a frequency with the value set in

H6-02 is input.

H6-04

Pulse Train Input Bias Sets the level of the value selected in H6-01

when 0 Hz is input.

H6-05

Pulse Train Input Filter

Time

Sets the pulse train input filter time

constant.

H6-06

Pulse Train Monitor

Terminal MP Selection

Select the pulse train monitor output

function (value of the o-oo part of

Uo-oo).

Example: Select “501” for monitor U5-01.

Select “0” when not using this parameter or

when using in the through mode.

H6-07

Pulse Train Monitor

Scaling

Sets the terminal MP output signal

frequency when the monitor value is 100%.

For example, to have the pulse train monitor

output equal the output frequency, set

H6-06 to 102 and H6-07 to 0.

H6-08

Pulse Train Input

Minimum Frequency

Sets the minimum frequency for the pulse

train input to be detected. Enabled when

H6-01 = 0, 1, or 2.

L1-01

Motor Overload

Protection Selection

0: Disabled

1: General purpose motor (standard fan

cooled)

2: Drive dedicated motor with a speed range

of 1:10

3: Vector motor with a speed range of 1:100

6: General purpose motor (50 Hz)

L1-02

Motor Overload

Protection Time

Sets the motor thermal overload protection

(oL1) time.

L1-03

Motor Overheat Alarm

Operation Selection

(PTC input)

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the

deceleration time in C1-09)

3: Alarm only (“oH3” will flash)

L1-04

Motor Overheat Fault

Operation Selection

(PTC input)

0: Ramp to stop

1: Coast to stop

2: Fast Stop (decelerate to stop using the

deceleration time in C1-09)

L1-05

Motor Temperature

Input Filter Time (PTC

input)

Adjusts the filter for the motor temperature

analog input (H3-02 or H3-10 = E).

L1-13

Continuous

Electrothermal

Operation Selection

0: Disabled

1: Enabled

2: Enabled (RTC)

L1-22

Leakage Current Filter

Time Constant 1

Sets the time constant for reducing the

sensitivity level when detecting leakage

current. Set in seconds and used when

operating at constant speed.

L1-23

Leakage Current Filter

Time Constant 2

Sets the time constant for reducing the

sensitivity level when detecting leakage

current. Set in seconds and used during

acceleration and deceleration operation.

L2-01

Momentary Power

Loss Operation

Selection

0: Disabled. Drive trips on Uv1 fault when

power is lost.

1: Recover within the time set in L2-02. Uv1

will be detected if power loss is longer than

L2-02.

2: Recover as long as CPU has power.

Uv1 is not detected.

L2-02

Momentary Power

Loss Ride-Thru Time

Sets the Power Loss Ride-Thru time.

Enabled only when L2-01 = 1 or 3.

No.

Name

Description

L2-03

Momentary Power

Loss Minimum

Baseblock Time

Sets the minimum wait time for residual

motor voltage decay before the drive output

reenergizes after performing Power Loss

Ride-Thru.

L2-04

Momentary Power

Loss Voltage Recovery

Ramp Time

Sets the time for the output voltage to return

to the preset V/f pattern during Speed

Search.

L2-05

Undervoltage

Detection Level (Uv1) Sets the DC bus undervoltage trip level.

L2-06

KEB Deceleration

Time

Sets the time required to decelerate from the

speed when KEB was activated to zero

speed.

L2-07

KEB Acceleration

Time

Sets the time to accelerate to the frequency

reference when momentary power loss is

over. If set to 0.0, the active acceleration

time is used.

L2-08

Frequency Gain at

KEB Start

Sets the percentage of output frequency

reduction at the beginning of deceleration

when the KEB Ride-Thru function is

started.

L2-11

DC Bus Voltage

Setpoint during KEB

Sets the desired value of the DC bus voltage

during KEB Ride-Thru.

L3-01

Stall Prevention

Selection during

Acceleration

0: Disabled.

1: General purpose. Acceleration is

paused as long as the current is above the

L3-02 setting.

2: Intelligent. Accelerate in the shortest

possible time without exceeding the L3-02

level.

L3-02

Stall Prevention Level

during Acceleration

Used when L3-01 = 1 or 2. 100% is equal

to the drive rated current.

L3-03

Stall Prevention Limit

during Acceleration

Sets Stall Prevention lower limit during

acceleration when operating in the constant

power range. Set as a percentage of drive

rated current.

L3-04

Stall Prevention

Selection during

Deceleration

0: Disabled. Deceleration at the active

deceleration rate. An ov fault may occur.

1: General purpose. Deceleration is paused

when the DC bus voltage exceeds the Stall

Prevention level.

2: Intelligent. Decelerate as fast as possible

while avoiding ov faults.

3: Stall Prevention with braking resistor.

Stall Prevention during deceleration is

enabled in coordination with dynamic

braking.

4: Overexcitation Deceleration.

Decelerates while increasing the motor

flux.

7: Overexcitation Deceleration 3. Applies

more braking power than normal

overexcitation deceleration. Yaskawa

recommends extra caution due to the heavy

load on the motor.

L3-05

Stall Prevention

Selection during Run

0: Disabled. Drive runs at a set

frequency. A heavy load may cause speed

loss.

1: Decel time 1. Uses the deceleration time

set to C1-02 while Stall Prevention is

performed.

2: Decel time 2. Uses the deceleration time

set to C1-04 while Stall Prevention is

performed.

L3-06

Stall Prevention Level

during Run

Enabled when L3-05 is set to 1 or 2. 100%

is equal to the drive rated current.

L3-11

Overvoltage

Suppression Function

Selection

0: Disabled

1: Enabled

L3-17

Target DC Bus Voltage

for Overvoltage

Suppression and Stall

Prevention

Sets the desired value for the DC bus

voltage during overvoltage suppression and

Stall Prevention during deceleration.

i.9 Parameter Table

94

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide