I.9 parameter table – Yaskawa iQpump Micro Quick Start User Manual

Page 98

Advertising
background image

No.

Name

Description

P1-18

Prime Loss Detection

Method

0: Current (A)

1: Power (kW)

2: Torque (%)

P1-19

Prime Loss Level

Detects loss of prime in the pump when in

Auto or Sleep Boost Mode.

P1-20

Loss of Prime Time

Sets the delay time before a “Loss of Prime”

condition occurs. The pump protection

criteria set in P1-18 and P1-19 must be met

before the timer will start.

P1-21

Loss of Prime

Frequency

Sets the frequency level above which the

“Loss of Prime” detection is enabled when

set to a value other than 0.

P1-22

Loss of Prime

Selection

0: Fault

1: Alarm

2: Digital out only

P1-23

Loss of Prime

Maximum Restart

Time after Fault

Sets the time in minutes that the drive will

wait before attempting another restart when

the restart fails or is not attempted due to a

continuing fault condition.

P1-30

Low Water Digital

Input Configuration

0: Normally open

1: Normally closed

P1-31

High Water Digital

Input Configuration

0: Normally open

1: Normally closed

P2-01

Sleep Level Type

0: Output frequency

1: Output current

2: Feedback

3: Output speed (RPM)

Note:

Feedback depends on PID

direction operation.

P2-02

Sleep Level

Sleep activates when the selected level type

(P2-01 setting) reaches the programmed

sleep level for the time set in P2-03.

P2-03

Sleep Delay Time

Sets the delay time before the drive enters

Sleep Mode when the sleep level set in

P2-02 is reached.

P2-04

Sleep Activate Level

Sets the level above which the output

frequency must rise to activate the sleep

function when P2-01, Sleep Level Type, is

set to 0 (Output Frequency / Speed).

P2-05

Sleep Boost Level

Sets the amount of boost applied to the

setpoint before going to sleep.

Setting this parameter to 0.0 disables the

function.

P2-06

Sleep Boost Hold Time

Sets the amount of time that the boosted

pressure will be maintained before the drive

goes to sleep.

P2-07

Sleep Boost Maximum

Time

Sets the amount of time that the system

(feedback) has to reach the boosted

setpoint. The drive will go to sleep when the

amount of time set in this parameter has

been exceeded.

P2-08

Delta Sleep Feedback

Drop Level

If the PID Error (setpoint minus feedback)

exceeds the level programmed in this

parameter within the time window set in

P2-09 and the output frequency is greater

than the level set in P1-06, the sleep

operation deactivates and the drive returns

to normal operation.

P2-09

Feedback Detection

Drop Time

Defines the time window in which the

software monitors the feedback to detect a

flow/no-flow condition.

P2-10

Sleep Mode: Cycling

Protection

Sets the maximum number of cycles that are

allowed within the time specified in P2-11

before tripping the PoC “Pump Over Cycle”

fault.

P2-11

Sleep Mode:

Maximum Cycling

Protection Time

Sets the maximum time allowed between

cycles. When no cycling occurs within the

programmed time, the drive will decrease

the internal cycle register.

No.

Name

Description

P2-12

Over Cycling Mode

0: Disabled

1: Alarm

2: Fault

3: Auto SP Compensation

P2-13

Setpoint

Compensation

Allows for the software to automatically

compensate the setpoint in the event of

excessive cycling.

P2-14

Maximum Setpoint

Compensation

Sets the maximum allowed setpoint

compensation for over-cycling function.

P2-23

Anti-No-Flow

Bandwidth

Sets the amount of PI error bandwidth used

to detect the Anti-No-Flow condition.

P2-24

Anti-No-Flow

Detection Time

Sets the time delay before the drive starts

the increased deceleration rate after Anti-

No-Flow is detected.

P2-25

Anti-No-Flow Release

Level

Sets the amount below the setpoint which

the feedback must drop to disengage the

Anti-No-Flow and return to normal PI

operation.

P4-01

Pre-Charge Level

Runs the drive at the frequency set in P4-02.

P4-02

Pre-Charge Frequency Sets the frequency reference used when the

Pre-Charge function is active.

P4-03

Pre-Charge Time

Sets the time at which the drive will spend

at the Pre-Charge Frequency 1 during pre-

charge. Maximum pre-charge time is P4-03

+ P4-07.

P4-05

Pre-Charge Loss of

Prime Level

Detects loss of prime in the pump during

Pre-charge 1.

When the measured quantity determined by

P1-18 drops below this level for the time set

in P1-20 and the output frequency is at the

level set in P4-02, a “Loss of Prime”

condition occurs.

The drive responds to the “Loss of Prime”

condition depending on the setting of

P1-22, Loss of Prime Selection.

P4-06

Pre-Charge Frequency

2

Sets the frequency reference used when the

Pre-Charge function 2 is active.

Setting this parameter to 0.0 disables the

function.

P4-07

Pre-Charge Time 2

Sets the time at which the drive will spend

at the Pre-Charge frequency 2 during pre-

charge. Maximum pre-charge time is P4-03

+ P4-07.

P4-08

Pre-Charge Loss of

Prime Level 2

Detects loss of prime in the pump.

When the measured quantity determined by

P1-18 drops below this level for the time set

in P1-20 and the output frequency is at the

level set in P4-06, a “Loss of Prime”

condition occurs.

The drive responds to the “Loss of Prime”

condition depending on the setting of

P1-22, Loss of Prime Selection.

P4-10

AUTO Mode Operator

Run Power Down

Storage

0: Disabled

1: Enabled

WARNING!Sudden Movement Hazard. If

the drive is powered down while running, it

will automatically initiate an internal Run

command upon power-up.

P4-11

Thrust Bearing

Acceleration Time

Sets the time at which the drive output

frequency will ramp up to the reference

frequency set in P4-12.

P4-12

Thrust Bearing

Frequency

The drive will accelerate to this frequency

in the time set to P4-11. The drive will

decelerate from the frequency in the time set

to P4-13.

i.9 Parameter Table

98

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide