P1-01: pump mode – Yaskawa iQpump Micro Quick Start User Manual

Page 76

Advertising
background image

Table i.23 Multi Setpoints 1 and 2

Multi Setpoint 1

(H1-0o = 8D)

Multi Setpoint 2

(H1-0o = 8E)

Setpoint Source

Open

Open

Frequency Ref (dependent on b1-01), Set-Point 1

- Q1-01 (when b1-01 = 0), Analog Setpoint

(H3-0o = C), Pulse Input Setpoint (H6-01 = 2),

or Memobus setpoint.

Closed

Open

Set Point 2 – Q1-02

Open

Closed

Set Point 3 – Q1-03

Closed

Closed

Set Point 4 – Q1-04

n

H2-01 to H2-03: Terminal MA/MB/MC, P1/PC, and P2/PC Function Selection

The drive has three multi-function output terminals.

No.

Parameter Name

Setting Range

Default

H2-01

Terminal MA, MB and MC Function Selection (relay)

0 to 1AA

E: Fault

H2-02

Terminal P1 Function Selection (open-collector)

0 to 1AA

37: During Frequency Output

H2-03

Terminal P2 Function Selection (open-collector)

0 to 1AA

E: Fault

Setting E: Fault

The output closes when the drive faults (excluding CPF00 and CPF01 faults).

Setting 37: During Frequency Output

The output closes when the drive is outputting a frequency.

Status

Description

Open

Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.

Closed

Drive is outputting frequency.

ON

ON

OFF

OFF

ON

OFF

ON

run command

baseblock

command

output

frequency

during run

during frequency

output

OFF

Figure i.41 During Frequency Output Time Chart

n

P1-01: Pump Mode

Selects the base operation mode of the drive controller.

No.

Parameter Name

Setting Range

Default

P1-01

Pump Mode

0, 3

0

Setting 0: Drive only

Designed for single pump stand-alone applications

Setting 3: MEMOBUS network

Up to eight drives can be networked together to provide for system redundancy and precise control.
Staging is disabled when and the drive PID output is influenced by the Water Level / Suction Pressure Control.
The functions listed below will behave slightly different when P1-01 is set to 3:
Start Level: Active on the first pump in the network. Drives in the process of alternation will not undergo this process.
Sleep: Active when the drive is the only drive running on the network.

i.6 Start-Up Programming and Operation

76

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide