I.9 parameter table – Yaskawa iQpump Micro Quick Start User Manual

Page 96

Advertising
background image

No.

Name

Description

L8-07

Output Phase Loss

Protection Selection

0: Disabled

1: Enabled (triggered by a single phase

loss)

2: Enabled (triggered when two phases are

lost)

L8-09

Output Ground Fault

Detection Selection

0: Disabled

1: Enabled

L8-10

Heatsink Cooling Fan

Operation Selection

0: During run only. Fan operates only

during run for L8-11 seconds after stop.

1: Fan always on. Cooling fan operates

whenever the drive is powered up.

L8-11

Heatsink Cooling Fan

Off Delay Time

Sets a delay time to shut off the cooling fan

after the Run command is removed when

L8-10 = 0.

L8-12

Ambient Temperature

Setting

Enter the ambient temperature. This value

adjusts the oL2 detection level.

L8-15

oL2 Characteristics

Selection at Low

Speeds

0: No oL2 level reduction below 6 Hz.

1: oL2 level is reduced linearly below 6

Hz. It is halved at 0 Hz.

L8-18

Software Current Limit

Selection

0: Disabled

1: Enabled

L8-19

Frequency Reduction

Rate during Overheat

Pre-Alarm

Specifies the frequency reference reduction

gain at overheat pre-alarm when L8-03 = 4.

L8-35

Installation Method

Selection

0: IP00/Open-Chassis enclosure

1: Side-by-Side mounting

2: IP20/NEMA Type 1 enclosure

3: Finless model drive or external heatsink

installation

L8-38

Carrier Frequency

Reduction

0: Disabled

1: Enabled below 6 Hz

2: Enabled for the entire speed range

L8-40

Carrier Frequency

Reduction Off Delay

Time

Sets the time that the drive continues

running with reduced carrier frequency

after the carrier reduction condition is gone.

Setting 0.00 s disables the carrier frequency

reduction time.

L8-41

High Current Alarm

Selection

0: Disabled

1: Enabled. An alarm is triggered at output

currents above 150% of drive rated current.

n1-01

Hunting Prevention

Selection

0: Disabled

1: Enabled

n1-02

Hunting Prevention

Gain Setting

If the motor vibrates while lightly loaded,

increase the gain by 0.1 until vibration

ceases. If the motor stalls, decrease the gain

by 0.1 until the stalling ceases.

n1-03

Hunting Prevention

Time Constant

Sets the time constant used for Hunting

Prevention.

n1-05

Hunting Prevention

Gain while in Reverse

Sets the gain used for Hunting Prevention.

If set to 0, the gain set to n1-02 is used for

operation in reverse.

n3-13

Overexcitation

Deceleration Gain

Applies a gain to the V/f pattern during

deceleration (L3-04 = 4). Returns to normal

values after ramp to stop or at re-

acceleration.

n3-21

High-Slip Suppression

Current Level

Sets output current level at which the drive

will start reducing the overexcitation gain

in order to prevent a too high motor slip

during Overexcitation Deceleration. Set as

a percentage of the drive rated current.

n3-23

Overexcitation

Operation Selection

0: Enabled in both directions

1: Enabled only when rotating forward

2: Enabled only when in reverse

o1-01

Drive Mode Unit

Monitor Selection

Selects the content of the last monitor that

is shown when scrolling through Drive

Mode display. Enter the last three digits of

the monitor parameter number to be

displayed: Uo-oo.

No.

Name

Description

o1-02

User Monitor Selection

after Power Up

1: Frequency reference (U1-01)

2: Direction

3: Output frequency (U1-02)

4: Output current (U1-03)

5: User-selected monitor (set by o1-01)

o1-03

Digital Operator

Display Selection

0: 0.01 Hz

1: 0.01% (100% = E1-04)

2: r/min (calculated using the number of

motor poles setting in E2-04)

3: User-selected units (set by o1-09, o1-10

and o1-11)

o1-05

LCD Contrast Control Sets the brightness of the optional LCD

operator.

o1-06

User Monitor Selection

Mode

0: 3 Monitor Sequential (displays the next

two sequential monitors)

1: 3 Monitor Selectable (set by o1-07 and

o1-08)

o1-07

Second Line Monitor

Selection

Selects the monitor that is shown in the

second line.

Enter the last three digits of the monitor

parameter number to be displayed: Uo-

oo. For example, set "403" to display

monitor parameter U4-03.

Note: Parameter is effective only when

o1-06 is set to 1.

o1-08

Third Line Monitor

Selection

Selects the monitor that is shown in the third

line.

Enter the last three digits of the monitor

parameter number to be displayed: Uo-

oo. For example, set "403" to display

monitor parameter U4-03.

Note: Parameter is effective only when

o1-06 is set to 1.

o1-09

Frequency Reference

Display Units

Sets unit display for the frequency reference

parameters and frequency related monitors

when o1-03 = 3.

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

15: “Hg (inches of mercury)

25: None

o1-10

User-Set Display Units

Maximum Value

These settings define the display values

when o1-03 is set to 3.

o1-10 sets the display value that is equal to

the maximum output frequency.

o1-11 sets the position of the decimal

position.

o1-11

User-Set Display Units

Decimal Display

o1-12

Home Help Text

0: Disabled

1: Enabled

o2-02

STOP Key Function

Selection

0: Disabled. STOP key is disabled in

REMOTE operation.

1: Enabled. STOP key is always enabled.

o2-03

User Parameter

Default Value

0: No change.

1: Set defaults. Saves parameter settings as

default values for a User Initialization.

2: Clear all. Clears the default settings that

have been saved for a User Initialization.

o2-04

Drive Model Selection Enter the drive model. Setting required only

if installing a new control board.

i.9 Parameter Table

96

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide