Factory Recommended Branch Circuit Protection for UL Compliance

Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.

Semiconductor protective type fuses are preferred.
Branch circuit protection shall be provided by any of the following according to

Table i.28

.

• Non-time Delay Class J, T, or CC fuses.
• Time Delay Class J, T, CC, or RK5 fuses.
• Semiconductor fuses.
• Molded Case Circuit Breakers (MCCB).

Table i.28 Factory Recommended Drive Branch Circuit Protection

Drive Model

Non-time Delay

Fuse Rating (A)

<1>

Time Delay Fuses

Bussmann

Semiconductor

Fuse Part Number
(Fuse Ampere)

<4>

MCCB

<5>

Class J, T, or CC

Fuse Rating (A)

<2>

Class RK5

Fuse Rating (A)

<3>

Rating (A)

Minimum

Enclosure

Volume (in

3

)

200 V Class Single-Phase Drives

BV0006

40

20

30

FWH-80B (80)

30

1152

BV0010

40

35

45

FWH-100B (100)

50

1152

BV0012

50

40

50

FWH-125B (125)

60

1152

BV0018

80

60

70

FWH-175B (175)

80

1152

200 V Class Three-Phase Drives

2V0006

20

10

15

FWH-25A14F (25)

15

1152

2V0010

25

15

20

FWH-70B (70)

25

1152

2V0012

25

20

30

FWH-70B (70)

30

1152

2V0020

40

40

50

FWH-90B (90)

60

1152

2V0030

60

80

FWH-100B (100)

90

1152

2V0040

90

110

FWH-200B (200)

125

1152

2V0056

110

150

FWH-200B (200)

150

2560

2V0069

125

175

FWH-200B (200)

200

2560

400 V Class Three-Phase Drives

4V0002

6

3.5

3

FWH-40B (40)

15

1152

4V0004

15

<6>

7

8

FWH-50B (50)

15

1152

4V0005

20

<7>

10

10

FWH-70B (70)

15

1152

4V0007

25

<8>

12

15

FWH-70B (70)

20

1152

4V0009

25

15

20

FWH-90B (90)

20

1152

4V0011

30

20

30

FWH-90B (90)

35

1152

4V0018

35

45

FWH-80B (80)

50

1152

4V0023

40

50

FWH-100B (100)

60

1152

4V0031

60

80

FWH-125B (125)

90

1152

4V0038

70

90

FWH-200B (200)

110

1152

<1> Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 4V0004, 4V0005, and 4V0007.
<2> Maximum 175% of drive input current rating for any Class J, T, or CC fuse.
<3> Maximum 225% of drive input current rating for any Class RK5 fuse.
<4> When using semiconductor fuses, Bussmann FWH are required for UL compliance.
<5> Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater.

Additionally, when using MCCBs for protection, the drive must be installed in a ventilated enclosure with minimum volume according the “Minimum
Enclosure Volume” column.

<6> Model 4V0004 requires Mersen (Ferraz) part number A6T15 for compliance.
<7> Model 4V0005 requires Mersen (Ferraz) part number A6T20 for compliance.
<8> Model 4V0007 requires Mersen (Ferraz) part number A6T25 for compliance.

n

Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external

power supply shall be a UL-Listed Class 2 power source or equivalent.

i.10 Standards Compliance

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide