Yaskawa iQpump Micro Quick Start User Manual

Page 34

Advertising
background image

Yaskawa recommends lowering the carrier frequency, particularly when audible noise is not a concern. The user can also

choose to reduce the load, increase the acceleration and deceleration times, or switch to a larger drive. This will help keep

peak current levels under 150%. Be sure to check the peak current levels when starting and stopping repeatedly during the

initial test run, and make adjustments accordingly.

n

Installation

Enclosure Panels

Keep the drive in a clean environment by installing the drive in an enclosure panel or selecting an installation area free of

airborne dust, lint, and oil mist. Be sure to leave the required space between drives to provide for cooling, and take proper

measures so the ambient temperature remains within allowable limits and keep flammable materials away from the drive.

Yaskawa offers protective designs for drives that must be used in areas subjected to oil mist and excessive vibration. Contact

Yaskawa or your Yaskawa agent for details.

Installation Direction

NOTICE: Install the drive upright as specified in the manual.

Refer to Mechanical Installation on page 39

for more information on

installation. Failure to comply may damage the drive due to improper cooling.

n

Settings

Upper Limits

NOTICE: The drive is capable of running the motor up to 400 Hz. Be sure to set the upper limit for the frequency of the drive to prevent the

possible danger of accidentally operating equipment at higher than rated speed. The default setting for the maximum output frequency is

60 Hz.

Lower Limits

NOTICE: Many pumps have a minimum safe operating speed. Be sure to properly set the minimum pump speed in to protect the pump

from damage.

DC Injection Braking

NOTICE: Excessive current during DC Injection Braking and excessive duration of DC Injection Braking can cause motor overheat.

Acceleration/Deceleration Times

Acceleration and deceleration times are affected by the amount of torque generated by the motor, the load torque, and the

inertia moment. Set a longer accel/decel time when Stall Prevention is enabled. The accel/decel times are lengthened for as

long as the Stall Prevention function is in operation.

n

General Handling

Wiring Check

NOTICE: Do not connect power supply lines to output terminals U/T1, V/T2, or W/T3. Failure to comply will destroy the drive. Be sure to

perform a final check of all sequence wiring and other connections before turning on the power and also check for short circuits on the

control terminals, which may damage the drive.

Selecting a Circuit Breaker or Circuit Interrupter

Yaskawa recommends installing a Ground Fault Circuit Interrupter (GFCI) to the power supply side. The GFCI should be

designed for use with AC drives (e.g., Type B according to IEC 60755).
Select a Molded Case Circuit Breaker (MCCB) or GFCI with a rated current 1.5 to 2 times higher than the drive rated input

current to avoid nuisance trips caused by harmonics in the drive input current.

Magnetic Contactor Installation

NOTICE: To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power supply

off and on more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.

Inspection and Maintenance

WARNING! Electrical Shock Hazard. Capacitors in the drive do not immediately discharge after shutting off the power. Wait for at least the

amount of time specified on the drive before touching any components after shutting off the power. Failure to comply may cause injury to

personnel from electrical shock.

WARNING! Burn Hazard. Because the heatsink can get very hot during operation, take proper precautions to prevent burns. When replacing

the cooling fan, shut off the power and wait at least 15 minutes to be sure that the heatsink has cooled down. Failure to comply may cause

burn injury to personnel.

Wiring

Yaskawa recommends using ring terminals on all drive models. UL/cUL approval requires the use of UL Listed closed-loop

crimp terminals when wiring the drive main circuit terminals. Use only the tools recommended by the terminal manufacturer

for crimping.

i.1 Preface

34

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide

Advertising