Digital Operator

Display

Alarm Name

High Feedback High FB

Sensed

(HIFB)

High Feedback Level Alarm

The feedback signal is too high.

LOP

Loss of Prime
The pump has lost its prime and P1-22 is set to 1.

Low City Pressure

(LCP)

Low City Pressure

Low Feedback Low FB

Sensed

(LoFb)

Low Feedback Level Alarm

The feedback signal is too low.

Low Suction Pressure

(LSP)

Low Suction Pressure

Low Water in Tank

(LWT)

Low Water in Tank

LT-1

Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.

Note:

An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F and

H2-oo = 10) are set.

LT-2

Capacitor Maintenance Time

The main circuit and control circuit capacitors are nearing the end of their expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

LT-3

Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

LT-4

IGBT Maintenance Time (50%)
IGBTs have reached 50% of their expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

NETSCAN

Waiting for Master

(NETSC)

NETSCAN

Drive is waiting for a message from the master.

NMS

(NOTSP)

Not Maintaining Setpoint
The setpoint cannot be maintained and P1-17 is set to 1.

oH

Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02.

oH2

Heatsink Overheat Warning
“Heatsink Overheat Warning” was input to a multi-function input terminal, S1 through S7 (H1-oo= B).

oH3

Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level (H3-02 or H3-10 = E).

oL1

Motor Overload
The electronic motor overload protection tripped

oL2

Drive Overload
The thermal sensor of the drive triggered overload protection.

oL3

Overtorque Detection 1
The current has exceeded the value set for Torque Detection Level 1 (L6-02) for longer than the allowable time (L6-03).

oL4

Overtorque Detection 2
The current has exceeded the value set for Torque Detection Level 2 (L6-05) for longer than the allowable time (L6-06).

ov

Control Circuit Overvoltage
Voltage in the control circuit exceeded the trip point.
• For 200 V class drives: approximately 410 V
• For 400 V class drives: approximately 820 V (740 V when E1-01 < 400)

PCyC

Pump Over Cycle

i.7 Troubleshooting

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide