Drive motor overload protection – Yaskawa iQpump Micro Quick Start User Manual

Page 104

Advertising
background image

Table i.29 Control Circuit Terminal Power Supply

Input / Output

Terminal Signal

Power Supply Specifications

Multi-function photocoupler output

P1, P2, PC

Requires class 2 power supply

Multi-function digital inputs

S1, S2, S3, S4, S5, S6, S7, SC

Use the internal power supply of the drive. Use class 2 for

external power supply.

Multi-function analog inputs

A1, A2, AC

Use the internal power supply of the drive. Use class 2 for

external power supply.

Pulse train input

RP

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

Pulse train output

MP

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

n

Drive Short-Circuit Rating

This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current

flow will not rise above 31,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives.
• The MCCB and breaker protection and fuse ratings shall be equal to or greater than the short-circuit tolerance of the power

supply being used.

• Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical amperes for 240 V in 200 V class

drives (up to 480 V for 400 V class drives) motor overload protection.

u

Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor

overload protection is UL Listed and in accordance with the NEC and CEC.

n

E2-01: Motor Rated Current

Setting Range: Model Dependent
Default Setting: Model Dependent
Parameter E2-01 (motor rated current) protects the motor if parameter L1-01 is not set to 0 (default is 1, standard induction

motor protection enabled).
If Auto-Tuning has been performed successfully, the motor data that was entered in T1-04 is automatically written into

parameter E2-01. If Auto-Tuning has not been performed, manually enter the correct motor rated current in parameter E2-01.

n

L1-01: Motor Overload Protection Selection

The drive has an electronic overload protection function (oL1) based on time, output current and output frequency, which

protects the motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an

external thermal overload relay for single motor operation.
This parameter selects the motor overload curve used according to the type of motor applied.

Table i.30 Overload Protection Settings

Setting

Description

0

Disabled

1

Standard Fan-Cooled Motor (Default)

2

Drive Duty Motor with a Speed Range of 1:10

3

Vector Motor with a Speed Range of 1:100

6

Standard Fan-Cooled Motor (50 Hz)

Disable the electronic overload protection (L1-01 = 0: Disabled) and wire each motor with its own motor thermal overload

when connecting the drive to more than one motor for simultaneous operation.
Enable the motor overload protection (L1-01 = “1”, “2”, or “3”) when connecting the drive to a single motor unless there is

another means of preventing motor thermal overload. The electronic thermal overload function causes an oL1 fault, which

shuts off the output of the drive and prevents additional overheating of the motor. The motor temperature is continually

calculated as long as the drive is powered up.

n

L1-02: Motor Overload Protection Time

Setting Range: 0.1 to 5.0 Minutes
Factory Default: 1.0 Minutes

i.10 Standards Compliance

104

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide