No.

Parameter Name

Setting Range

Default

b1-03

Stopping Method Selection

0 to 3

1

Setting 0: Ramp to Stop

When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the

active deceleration time. The default deceleration time is set to parameter C1-02.
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection, Zero Speed Control,

or Short Circuit Braking.

Setting 1: Coast to Stop

When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to

stop. The stopping time is determined by the inertia and the friction in the driven system.

Drive output is shut off

Run

command

Output

frequency

Motor speed

ON

OFF

Figure i.34 Coast to Stop

Note:

After a stop is initiated, any subsequent Run command entered will be ignored until the minimum baseblock time (L2-03) has expired. Do

not enter Run command until it has come to a complete stop. Use DC Injection at Start or Speed Search to restart the motor before it has

completely stopped.

Setting 2: DC Injection Braking to Stop

When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time

(L2-03). When the minimum baseblock time has expired, the drive will inject the amount DC Injection Braking is set in

parameter b2-02 into the motor windings to brake the motor. The stopping time in DC Injection Braking to Stop is significantly

faster compared to Coast to Stop.

Motor coasts

DC Injection Braking

with the current set in

b2-02

Run

command

Output

frequency

ON

OFF

Motor speed

Minimum Baseblock

Time (L2-03)

Figure i.35 DC Injection Braking to Stop

DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is

removed. It can be calculated by:

DC Injection brake time

(b2-04) x 10 x Output frequency

Max. output frequency (E1-04)

=

i.6 Start-Up Programming and Operation

YASKAWA TOEP YAIQPM 02B YASKAWA AC Drive - iQpump Micro Quick Start Guide

71